Siemens PAC3100 vs APM-96Z – Technical Comparison
| Parameters | Siemens PAC3100 | APM-96Z |
|---|---|---|
| Product Type | Power Monitoring Device | Economic Multifunction Power Meter |
| Order Number | 7KM3133-0BA00-3AA0 | APM-96Z |
| Mounting | 96 × 96 mm Panel Mount | 96 × 96 mm Panel Mount |
| Panel Cutout | 92 × 92 mm | Confirm mechanical drawing |
| Measurement System | 1P / 2P / 3P; 3-wire / 4-wire | 3P3W / 3P4W |
| Voltage Input | Up to 480 V L-L / 277 V L-N | 18–277 V L-N; 100 V PT secondary |
| Current Input | 5 A CT | 1 A / 5 A CT |
| Voltage & Current Accuracy | Class 1 | 0.5% |
| Active Energy Accuracy | Class 1 | Class 1.0 |
| Reactive Energy Accuracy | Class 3 | Class 2.0 |
| Harmonic Measurement | TRMS up to 15th harmonic | No individual harmonic measurement listed |
| Frequency | 50/60 Hz | 45–65 Hz |
| Communication | RS485 Modbus RTU | RS485 Modbus RTU |
| Ethernet | Not built in | Optional Ethernet interface; confirm exact configuration |
| Digital Inputs | 2 | Optional, up to 6 |
| Digital Outputs | 2 | Optional, up to 4 |
| Analog Outputs | Not listed | Optional, up to 3 |
| Pulse Output | Configurable digital output | Standard pulse output |
| Auxiliary Power | 100–240 V AC ±10%; 110–250 V DC ±10% | 85–265 V AC/DC |
| Display | Graphic LCD | LCD; optional LED display |
Key Differences Between PAC3100 and APM-96Z
| Key Difference | Siemens PAC3100 | Blue Jay APM-96Z |
|---|---|---|
| Voltage Input | Direct measurement up to 480 V L-L | Direct measurement up to 277 V L-N |
| CT Input | 5 A | 1 A / 5 A |
| Basic Measurement Accuracy | Class 1 | 0.5% |
| Reactive Energy Accuracy | Class 3 | Class 2 |
| Harmonics | TRMS up to 15th harmonic | Individual harmonic measurement not listed |
| Ethernet | No integrated Ethernet | Optional Ethernet |
| I/O Configuration | 2 DI / 2 DO | Optional 6 DI / 4 DO / 3 AO |
| Display | Graphic LCD | LCD or optional LED |
When Is APM-96Z a Suitable Replacement for PAC3100?
APM-96Z is worth considering in the following applications:
| Application | Suitability | Key Consideration |
|---|---|---|
| 400/230 V three-phase distribution monitoring |
Suitable for evaluation
|
Direct voltage input and 5 A CT configuration |
| Factory energy consumption monitoring |
Suitable for evaluation
|
RS485 Modbus RTU integration |
| Commercial building power monitoring |
Suitable for evaluation
|
Voltage and CT configuration |
| OEM electrical panel manufacturing |
Suitable for evaluation
|
96 × 96 mm panel format and optional I/O |