Siemens PAC3220 vs Blue Jay APM-96J – Technical Specification
| Parameters | Siemens PAC3220 | APM-96J |
|---|---|---|
| Product Type | Power Monitoring Device | Multifunction Power Meter |
| Mounting | Panel Mount | Panel Mount |
| Front Dimensions | 96 × 96 mm | 96 × 96 mm |
| Panel Cutout | 92 × 92 mm | Confirm mechanical drawing |
| Measurement System | 1P2W / 3P3W / 3P4W | 1P2W / 2P3W / 3P3W / 3P4W |
| Voltage Input | 57.7/100–400/690 V | Direct: 18–277 V L-N; PT secondary: 100 V |
| Current Input | 1 A / 5 A CT | 1 A / 5 A CT |
| Voltage Accuracy | Class 0.2 | 0.2% |
| Current Accuracy | Class 0.2 | 0.2% |
| Active Power Accuracy | Class 0.2 | 0.5% stated |
| Reactive Power Accuracy | Class 1 | 0.5% stated |
| Active Energy Accuracy | Class 0.5 | Class 0.5S |
| Reactive Energy Accuracy | Class 2 | Class 1.0 |
| Frequency | 45–65 Hz | 45–65 Hz |
| Communication | 2 × Ethernet, Modbus TCP | RS485 Modbus RTU |
| Optional Communication | RS485 / PROFIBUS expansion modules | Ethernet Modbus TCP / Profibus |
| Digital Inputs | 2 | Up to 6, optional |
| Digital Outputs | 2 | Up to 4, optional |
| Analog Outputs | Optional expansion module | 2-channel, optional |
| Harmonic Measurement | THD measurement | THD and individual harmonics up to 63rd |
| TOU Function | Peak/off-peak energy counters | Time-of-use energy metering |
| Auxiliary Power | 100–250 V ±10% AC/DC (standard version) | 85–265 V AC/DC; optional 20–60 V DC |
| Display | Graphic LCD | Backlit LCD |