Janitza UMG 103-CBM Compact Energy Analyzer

The Janitza UMG 103-CBM is a compact energy analyzer designed for electrical monitoring and data acquisition in industrial and commercial power distribution systems. It provides three-phase electrical measurement, harmonic analysis up to the 40th order, and Class 0.5S active energy accuracy.

With RS485 Modbus RTU communication and 4 MB internal data memory, the UMG 103-CBM records energy and measurement profiles for long-term monitoring. Its self-powered measurement design and compact installation make it suitable for distributed energy monitoring applications.

Contact us

Key Features

  • Three-phase electrical measurement.
  • Harmonic analysis up to the 40th order.
  • Class 0.5S active energy accuracy.
  • 4 MB internal memory.
  • RS485 Modbus RTU.
  • Up to 400,000 recorded measured values under specified profile settings.
  • Min/Max and operating value storage.
  • Integrated comparator functions.
  • No separate auxiliary supply required.

Technical Specifications

Parameters UMG 103-CBM
Product Type Compact Energy Analyzer
Mounting DIN Rail / Compact Installation
Current Input 1 A / 5 A CT
Active Energy Accuracy Class 0.5S
Harmonics Up to 40th
Memory 4 MB
Recorded Values Up to 400,000
Communication RS485
Protocol Modbus RTU
Digital I/O Check ordered configuration
Auxiliary Supply Self-powered
Additional Functions CREST factor, comparators, Min/Max

Cost-effective Alternative Solution for Janitza UMG 103-CBM

Selection point Janitza UMG 103-CBM APM-4MJ Replacement implication
Energy 0.5S at 5 A Manual states 0.5S Check required standard and the supplied input.
Harmonics Through 40th Through 63rd in selected manual Verify per-phase output and scaling.
Local archive 4 MB; clock and recorded measurement profiles SOE functions; equivalent profile archive unverified Use an independently specified logger if required.
Installation DIN; overview gives 71.5 mm width DIN; 72 × 110 × 66 mm drawing Check cover height and terminal clearance.
Supply and link No separate supply; RS-485 Modbus Separate 85–265 V AC/DC standard; RTU Provide power and rebuild polling.
Select the offered inputs Verify installed CT or sensor output and measuring voltage 1 A / 5 A / 100 mA options; select voltage rating Check polarity, ratio, burden and continuous ratings.
Select the offered supply Verify nameplate and actual supply extremes 85–265 V AC/DC standard; custom supply requires confirmation Supply rating is separate from measuring voltage.