SATEC PM175 EN 50160 Power Quality Analyzer

The SATEC PM175 is a power quality analyzer designed for monitoring and analyzing electrical system performance according to EN 50160 requirements. It combines multifunction power measurement with power quality monitoring, waveform capture, and event recording.

With Class 0.2S active energy accuracy, harmonic analysis up to the 50th order, and support for EN 50160 and GOST 32144 reporting, the PM175 helps users assess voltage quality and identify disturbances in utility substations and industrial electrical systems.

Its built-in RS485 communication, optional Ethernet and Profibus, and configurable digital and analog I/O support integration with SCADA and power management systems.

Contact us

Key Features

  • EN 50160 power quality monitoring and reports.
  • GOST 32144 reporting.
  • Class 0.2S active energy accuracy.
  • Harmonic analysis up to 50th order.
  • Interharmonics and flicker monitoring.
  • Waveform capture and event recording.
  • Time-of-use and multi-tariff metering.
  • RS485 and optional Ethernet / Profibus.
  • Programmable logic and alarm setpoints.
  • Up to 8 digital/analog I/O.

Technical Specifications

Parameters PM175
Product Type Power Quality Analyzer
Mounting Panel Mount / DIN Rail
Panel Cutout 92 × 92 mm
Current Input 1 A / 5 A / 40 mA HACS
Voltage Input 120–690 V AC nominal
Active Energy Accuracy Class 0.2S
Harmonics Up to 50th
Power Quality Standards EN 50160 / GOST 32144
Flicker IEC 61000-4-15
Waveform Capture Yes
Event Recording Yes
Sampling Rate 128 samples/cycle
Communication RS485 / RS232 / RS422
Optional Interfaces Ethernet / Profibus / Cellular Modem
Protocols Modbus / DNP3.0 / Profibus
Digital / Analog I/O Up to 8 I/O
Auxiliary Supply 85–265 V AC / 88–290 V DC standard

Cost-effective Alternative Solution for SATEC PM175

Selection point SATEC PM175 APM-96Q Replacement implication
Accuracy 0.2S per IEC 62053-22 Published 0.2 without S No 0.2S equivalence demonstrated.
PQ duties EN50160 / GOST reports; flicker and waveform events PQ functions and capture advertised Matching reports, event timing and methodology unverified.
Harmonics Through 50th; interharmonics listed Through 127th; interharmonic equivalence unverified Count alone does not establish a PQ replacement.
Sensors 1 A / 5 A, HACS and special sensor options Conventional 1 A / 5 A Special sensors require documented conversion or replacement.
Protocol / records RTU, DNP3, Profibus; programmable loggers RTU; optional TCP and logging Engineer utility protocols and archive requirements separately.
Select the offered inputs Verify installed CT or sensor output and measuring voltage 1 A / 5 A CT; select voltage rating Check polarity, ratio, burden and continuous ratings.
Select the offered supply Verify nameplate and actual supply extremes 85–265 V AC/DC standard; custom supply requires confirmation Supply rating is separate from measuring voltage.