DoblePRIME PD-Guard PD Monitoring System

Contact us

DoblePRIME PD-Guard can be used with a variety of different sensors, including acoustic detection antennas for partial discharge, CTs for single or multiple conductors, UHF oil drain valve probes for use within the equipment, and insulating bushing end screen connectors.

Features of DoblePRIME PD-Guard PD Monitoring System

  • Monitor partial discharge and configure monitor via computer, tablet, or web-enabled device
  • Works with a variety of sensors including antenna for airborne PD, CTs for individual or bundled conductors, UHF drain valve probes for in-tank applications and bushing tap connectors
  • Built-in Expert System learns PD behavior and indicates changes in frequency and/or severity of measured PD levels
  • Alarm relays for external notification
  • Broadband RF signal detection including peak, average, and quasi-peak

 

Benefits of DoblePRIME PD-Guard PD Monitoring System

  • Monitor PD in critical and high-risk assets
  • Save costly equipment by quickly reacting to rapid insulation deterioration warnings
  • Identify problem areas, diagnose the severity of the situation, and plan action and intervention
  • Plan for further testing, maintenance, and replacements in a proactive, risk management approach
  • Use as a standalone product, networked to an existing SCADA system, or as part of a DoblePRIME Condition Monitoring Platform

 

Specification of DoblePRIME PD-Guard PD Monitoring System

Inputs 4 or 8 channels, multiplexed
Connector BNC
Input impedance 5Ω
Dynamic range 60dB
Detection types Peak, quasi-peak and average detector
Sweep processing Continuous, average, max hold and differential
Bandwidth 50kHz to 50MHz
Resolution Bandwidth 9kHz/120kHz
Noise floor Approximately -90 dBm for peak detect or -100dBm for average detect(RBW 9kHZ)
AC synchronisation Wired Sync to external AC source
Storage 32GB eMMC Flash for application and data storage