Specifications of RM22-UA Overvoltage and Undervoltage Control Relay
Range of product | Harmony Control Relays |
---|---|
Relay type | Voltage control relay |
Product or component type | Voltage control relay |
Network number of phases | 1 phase |
Supply circuit type | DC |
Relay name | RM22UA |
Relay monitored parameters | Undervoltage and overvoltage in window mode Overvoltage or undervoltage detection |
time delay | Adjustable 0.1…30 s, +/- 10 % of the full scale value on crossing the threshold Tt |
Switching capacity in VA | 2000 VA |
Minimum switching current | 10 mA at 5 V DC |
Maximum switching current | 8 A AC |
Power consumption in VA | 3.5 VA AC |
Measurement range | 15…500 V voltage AC/DC 50/60 Hz |
Utilisation category | AC-15 conforming to IEC 60947-5-1 DC-13 conforming to IEC 60947-5-1 AC-1 conforming to IEC 60947-4-1 DC-1 conforming to IEC 60947-4-1 |
Contacts type and composition | 2 C/O |
Reset time | 1500 ms at maximum voltage |
---|---|
Maximum switching voltage | 250 V AC |
Supply voltage limits | 20.4…264 V AC/DC |
Maximum power consumption in W | 1.5 W DC |
Immunity to microbreaks | 10 ms |
Resistance across terminals | 150 kOhm at E2-M terminals 300 kOhm at E1-M terminals 500 kOhm at E3-M terminals |
Output contacts | 2 C/O |
Nominal output current | 8 A |
Maximum measuring cycle | 100 ms measurement cycle as true rms value |
Hysteresis | 3 % fixed of full scale for window mode 5…50 % adjustable of threshold setting |
delay at power up | 600 ms |
Repeat accuracy | +/- 0.5 % for input and measurement circuit +/- 2 % for time delay |
Measurement error | < 1 % over the whole range with voltage variation 0.05 %/°C with temperature variation |
Response time | <= 500 ms |
Overvoltage category | III conforming to IEC 60664-1 |
Insulation resistance | > 100 MOhm at 500 V DC |
insulation | Between supply and measurement |
Connections – terminals | Screw terminals, 2 x 0.5…2 x 2.5 mm² (AWG 20…AWG 14) solid without cable end Screw terminals, 2 x 0.2…2 x 1.5 mm² (AWG 24…AWG 16) flexible with cable end Screw terminals, 1 x 0.5…1 x 3.3 mm² (AWG 20…AWG 12) solid without cable end Screw terminals, 1 x 0.2…1 x 2.5 mm² (AWG 24…AWG 14) flexible with cable end |
Tightening torque | 0.6…1 N.m conforming to IEC 60947-1 |
Housing material | Self-extinguishing plastic |
Mounting support | 35 mm DIN rail conforming to IEC 60715 |
Electrical durability | 100000 cycles |
Mechanical durability | 10000000 cycles |
Contacts material | Cadmium free |
Safety reliability data | MTTFd = 308.2 years B10d = 290000 |
Width | 22.5 mm |
Net weight | 0.11 kg |
Functionality | Undervoltage and overvoltage in window mode |
Compatibility code | RM22 |
Electromagnetic compatibility | Immunity for residential, commercial and light-industrial environments conforming to IEC 61000-6-1 Immunity for industrial environments conforming to IEC 61000-6-2 Emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3 Emission standard for industrial environments conforming to IEC 61000-6-4 Electrostatic discharge – test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2 Electrostatic discharge – test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test – test level: 10 V/m level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test – test level: 4 kV level 4 (direct) conforming to IEC 61000-4-4 Electrical fast transient/burst immunity test – test level: 2 kV level 4 (capacitive coupling) conforming to IEC 61000-4-4 Surge immunity test – test level: 4 kV level 4 (common mode) conforming to IEC 61000-4-5 Surge immunity test – test level: 2 kV level 4 (differential mode) conforming to IEC 61000-4-5 Conducted and radiated emissions class B group 1 conforming to CISPR 11 Conducted and radiated emissions class B conforming to CISPR 22 |
---|---|
Standards | IEC 60255-1 |
product certifications | RCM UL EAC CSA CE GL CCC |
Ambient air temperature for storage | -40…70 °C |
Ambient air temperature for operation | -20…50 °C at 60 Hz -20…60 °C at 50 Hz |
Relative humidity | 93…97 % at 25…55 °C conforming to IEC 60068-2-30 |
Vibration resistance | 0.075 mm (f= 10…58.1 Hz) not in operation conforming to IEC 60068-2-6 1 gn (f= 10…58.1 Hz) not in operation conforming to IEC 60068-2-6 0.035 mm (f= 58.1…150 Hz) in operation conforming to IEC 60068-2-6 0.5 gn (f= 58.1…150 Hz) in operation conforming to IEC 60068-2-6 |
Shock resistance | 15 gn (duration = 11 ms) for not in operation conforming to IEC 60068-2-27 5 gn (duration = 11 ms) for in operation conforming to IEC 60068-2-27 |
IP degree of protection | IP20 (terminals) conforming to IEC 60529 IP40 (housing) conforming to IEC 60529 IP50 (front panel) conforming to IEC 60529 |
Pollution degree | 3 conforming to IEC 60664-1 |
Dielectric test voltage | 2.5 kV, 1 min AC 50 Hz conforming to IEC 60255-27 |