Feature:
- 6″ probe length
- Field selectable ranges from 250FPM (1.25m/s) to 15,000FPM (75m/s) suit any application
- Easy push button set-up reduces installation time
- Compact housing minimizes installation footprint
- 4-20 mA output for use with most building management systems
- Digital filter for signal damping
- Selectable 0.5 to 15 (seconds) output filter
- 1/2˝ male NPT process connection and screw terminal electrical connection
- Maximum 300mA current consumption and 600 ohm loop resistance
- Unit not position sensitive, probe must be aligned with airflow
Application:
- Exhaust stack flow monitoring
- Air control in drying processes
- HVAC air velocity measurements
- Fan supply and exhaust tracking
- Clean room fresh air supply
- Ensure proper lab hood exhaust flow rates
Specification
- Service: Clean air and compatible, non-combustible gases.
- Accuracy: 3% FS Process gas: 32 to 122°F (0 to 50°C); 4% FS Process gas: -40 to 32°F & 122 to 212°F (-40 to 0°C & 50 to 100°C).
- Response Time: Flow: 1.5 seconds to 95% of final value (output filter set to minimum).
- Temperature Limits: Process: -40 to 212°F (-40 to 100°C). Ambient: 32 to 140°F (0 to 60°C).
- Pressure Limit: 100 psi (6.89 bar) maximum.
- Humidity Limit: Non-condensing.
- Power Requirements: 12-35 VDC, 10-16 VAC. 1.5 A rating required on supply due to initial power surge drawn by transmitter.
- Output Signal: 4-20 mA, isolated 24V source, 3 or 4-wire connection.
- Output Filter: Selectable 0.5-15 (seconds).
- Loop Resistance: 600 ohms max.
- Current Consumption: 300 mA max.
- Electrical Connections: Screw terminal.
- Process Connections: 1/2″ male NPT.
- Enclosure Rating: Designed to meet NEMA 4X (IP66) for non LED models only.
- Mounting Orientation: Unit not position sensitive. Probe must be aligned with airflow.
- Weight: 12.6 oz (357.2 g).
- Agency Approvals: CE.
- OPTIONAL DISPLAY VERSION:
- Display: 4-1/2 digit 1/2″ red LED.
- Resolution: 1 FPM, 0.01 MPS (10 FPM @ 10,000 and 15,000 FPM ranges).
- Weight: 13.3 oz (377 g).