AIM-D100-T Series Universal DC Insulation Monitor

IM-D100-T series DC insulation monitor can be applied in a 10~1000V DC system, which is used to monitor the insulation resistance of the positive and negative poles to the ground of the DC ungrounded system online, and send out an early warning or alarm signal when the insulation resistance is lower than the set value.

The product is based on the principle of unbalanced bridge, which avoids the problem that the balance bridge cannot detect the insulation resistance when there is a ground fault at the positive and negative poles at the same time.

The products can be used in DC systems such as power generation manufacturers, DC panels of substations, electric vehicle charging devices, UPS power supply systems, photovoltaic DC systems, energy storage systems and other DC power grids.

Contact us

Feature

  • LED indication function. The product panel has operation, communication and fault, overvoltage, and undervoltage LEDs, which can display the product status.
  • LCD display function. The product adopts 128*32 dot matrix liquid crystal display, which can display parameter information.
  • Relay output function. The product has 3 relay outputs, and can choose normally open or normally closed mode.
  • Event logging function. The product can record the time of alarm occurrence and the type of fault, which is convenient for staff to troubleshoot.
  • Communication networking function. The product has 1 RS485 interface and adopts Modbus-RTU protocol, which can be used for data interaction.
  • Rail mounting. The product is installed on a standard 35mm guide rail.
  • Plug and unplug the terminals. The product adopts plug-in terminal wiring, which is convenient for wiring and installation.

 

Specification

Item Technical Specifications
Auxiliary power supply DC 9~36V
The maximum power consumption ≤6W
Voltage monitoring Voltage range AIM-D100-TH:DC 100~1000V;

AIM-D100-TL:DC 10~100V

Measurement accuracy 0.5 class
Overvoltage threshold ≥ 110% of rated voltage
Undervoltage threshold ≤90% of rated voltage
Insulation monitoring insulation resistance range 1kΩ~10MΩ
The early warning alarm range 10kΩ~10MΩ
Measurement accuracy 1~10kΩ:±1k;10k~500k:≤3%
System leakage capacitance ≤5μF
Insulation monitoring mode Periodic trigger 5~500s delay can be set;

Communication trigger: read on demand

Insulation monitoring time 500ms/time, 1000ms/time
Internal DC impedance <1MΩ
Alarm mode LCD, LED indicator, relay output
Alarm output 3 groups of relay outputs, normally open or normally closed can be set