Schneider Electric PowerLogic PM5110 Power Meter

The Schneider Electric PowerLogic PM5110 is a widely adopted 96×96 panel-mounted power meter with Class 0.5S active energy accuracy. It measures key electrical parameters and harmonics up to the 15th order, equipped with RS485 Modbus RTU communication, 1 digital output and 33 configurable alarms for energy monitoring and basic power quality management in commercial and industrial panels.

Contact us

Some panel builders and system integrators are sourcing drop-in alternatives for retrofitting and new projects. We offer the APM-96J as a direct replacement power meter for the PM5110.

Specifications between Schneider PowerLogic PM5110 and APM-96J

Selection point Schneider PM5110 Blue Jay APM-96J What this means for replacement
Nominal CT input 1 A / 5 A 1 A / 5 A options Order the installed CT secondary; verify measurement and overload limits.
Active-energy class IEC 62053-22 Class 0.5S Published Class 0.5S Obtain accuracy documentation for the supplied configuration.
Voltage measurement Reference: 20-400 V L-N; 35-690 V L-L wye 18-277 V AC L-N on product page Check terminal voltage and wiring; use appropriate VTs outside the selected rating.
Control power Reference nominal: 100-415 V AC; 125-250 V DC; check tolerances 85-265 V AC/DC standard; other options require confirmation Compare actual supply extremes; change the supply design where required.
Opening and depth 96 mm front; verify installed opening; product depth 72 mm Manual cut-out 91 +0.8 x 91 +0.8 mm; depth drawing 74 mm Confirm the existing opening and clamp engagement; specify an adapter if needed.
Harmonics Up to 15th Manual version up to 63rd Specify the required individual harmonics and test their registers.
Pulse and alarms 1 digital output; 33 configurable alarms Pulse configuration; optional DI/DO; manual lists 5 alarm thresholds Specify the pulse circuit and the alarm conditions actually used.
Current range Product specification up to 8.5 A 5 A option: measurement 1.2 x rated = 6 A Check operation above rated CT current before keeping the existing ratio.

PM5110 replacement configuration

Check and configure the replacement

1 Keep the CT circuit correctly rated

Record the CT secondary and ratio, network connection and actual phase-to-neutral voltage. Select the corresponding hardware input and any required VTs; a menu setting does not change the hardware rating.

2 Plan the panel and supply changes

Measure the opening, panel thickness and rear clearance against the APM drawing. Its stated opening differs from the front dimensions. Confirm the full supply variation and the terminal arrangement.

3 Transfer the measurements and outputs

Rebuild the Modbus point list, including the individual harmonics required by your process. Match units, energy direction, word order and scaling. Configure the required pulse output and active alarms.

4 Accept the replacement on the values you use

Check local and remote voltage, current, power and accumulating energy against an appropriate reference. Verify pulse counts and alarm operation before the feeder returns to normal monitoring.

Applications for this replacement

Suitable for plant feeder monitoring, OEM control panels and panel repairs where the controller can use a new Modbus point map. Projects using the complete original alarm set or extended input range need a configured solution that covers those requirements.

Request the configuration and purchase quote

Send reference METSEPM5110, the CT ratio, measured voltage, auxiliary-supply range and quantity. Attach the panel opening dimensions, a terminal photo, the required Modbus points and any pulse counter specification. Request an APM-96J offer identifying the hardware input, supply, pulse and I/O options, accuracy documentation, drawing and register map.