Siemens PAC3120 vs. Blue Jay APM-96J – Technical Comparison
Similarities Between PAC3120 and APM-96J
Both meters share several core functions, making APM-96J worth evaluating for selected PAC3120 applications.
| Comparison | Siemens PAC3120 | Blue Jay APM-96J |
|---|---|---|
| Product Type | Multifunction Power Monitoring Device | Multifunction Power Meter |
| Mounting | 96 × 96 mm panel | 96 × 96 mm panel |
| Measurement System | Three-phase | Three-phase |
| Current Input | 1 A / 5 A CT | 1 A / 5 A CT |
| Communication | RS485 Modbus RTU | RS485 Modbus RTU |
| Voltage Measurement | Yes | Yes |
| Current Measurement | Yes | Yes |
| Active Power | Yes | Yes |
| Reactive Power | Yes | Yes |
| Frequency Measurement | Yes | Yes |
| Active Energy Measurement | Yes | Yes |
| Digital I/O | 2 DI / 2 DO | Optional DI/DO |
What this means: Both products support the core functions needed for three-phase electrical measurement and Modbus RTU-based monitoring. APM-96J can therefore be considered for projects where these functions are the primary requirements.
Key Differences Between PAC3120 and APM-96J
| Comparison | Siemens PAC3120 | APM-96J |
|---|---|---|
| Rated Voltage | 400 V L-N / 690 V L-L | Direct: 18–277 V L-N; PT secondary: 100 V |
| Active Energy Accuracy | Class 0.5 | Class 0.5S |
| Reactive Energy Accuracy | Class 2 | Class 1.0 |
| Auxiliary Power | 100–250 V ±10% AC/DC | 85–265 V AC/DC; optional 20–60 V DC |
| Harmonic Analysis | Not specified in the cited datasheet | Individual harmonics up to 63rd order |
| THD Measurement | Not specified in the cited datasheet | Voltage and current THD |
| Time-of-Use (TOU) | Not listed in the cited datasheet | Supported |
| Communication Options | RS485 Modbus RTU | RS485 Modbus RTU; optional Ethernet Modbus TCP / Profibus |
| Analog Outputs | Not listed | Optional 2-channel 0/4–20 mA |
| Digital I/O | 2 DI / 2 DO | Optional up to 6 DI / 4 DO |
What to Check Before Replacing Siemens PAC3120?
Although APM-96J shares several measurement and communication functions with PAC3120, replacement requires checking the following details.
| Replacement Consideration | What You Need to Check |
|---|---|
| Voltage Input | Confirm whether direct measurement or an external PT is required |
| CT Compatibility | Select the 1 A or 5 A input according to the existing CT |
| Auxiliary Power | Confirm that the available supply is within the APM-96J operating range |
| Communication | Check Modbus register mapping and communication settings |
| Accuracy | Verify that APM-96J accuracy meets the project’s requirements |
| Installation | Confirm panel cutout, installation depth, and terminal positions |
| Digital I/O | Check whether the existing system uses the original DI/DO functions |
Important voltage consideration: If your existing PAC3120 is installed in a 690/400 V system, do not connect the 400 V line-to-neutral voltage directly to the APM-96J. An appropriately rated PT and compatible secondary voltage configuration are required.