Siemens PAC4200 Multifunction Power Meter

The Siemens PAC4200 is a multifunction power monitoring device designed for three-phase electrical systems. With PAC4200 entering its product phase-out, existing users may need an alternative for equipment replacement, ongoing maintenance, or new projects.

Looking for an alternative to Siemens PAC4200? The APM-96Q is worth considering for selected applications, offering comprehensive electrical measurement, advanced harmonic analysis, and flexible communication options. support KM4212-0BA00-2AA0, 7KM4211-1BA00-3AA0, 7KM4212-0BA00-3AA0.

Contact us

Siemens PAC4200 VS APM-96Q Specification Comparison

Parameters Siemens PAC4200 APM-96Q
Product Type Power Monitoring Device Multifunction Power Analyzer
Mounting Panel Mount Panel Mount
Front Dimensions 96 × 96 mm 96 × 96 mm
Measurement System Three-phase Three-phase
Voltage Input 400 V L-N / 690 V L-L 100 V / 220 V / 380 V versions
Current Input 5 A CT 1 A / 5 A CT
Voltage Accuracy Class 0.2 ±0.1% stated
Current Accuracy Class 0.2 ±0.1% stated
Active Power Accuracy Class 0.2 0.2 stated
Reactive Power Accuracy Class 1.0 0.5 stated
Active Energy Accuracy Class 0.2 under IEC 62053-22 (version/standard dependent) 0.2 stated
Reactive Energy Accuracy Class 2.0 Class 1.0
Frequency 45–65 Hz 40–65 Hz
Harmonic Measurement Voltage: 2nd–64th; current: 3rd–31st Up to 127th on specified version
THD Measurement Voltage and current Voltage and current
Communication Ethernet Modbus TCP RS485 Modbus RTU
Optional Communication RS485 / PROFIBUS / PROFINET Ethernet Modbus TCP / RTU
Digital Inputs 2 standard 1–6 optional
Digital Outputs 2 standard 1–4 optional
Analog Outputs Optional expansion 1–3 optional
Auxiliary Power 95–240 V AC / 110–340 V DC 85–265 V AC/DC
Optional Auxiliary Power 22–65 V DC 48 V DC / 380 V AC customized
Display LCD 320 × 240 color LCD

What to Check Before Replacing Siemens PAC4200?

Although APM-96Q offers several comparable measurement and monitoring functions, it should not be treated as a plug-and-play replacement for PAC4200.

Before selecting a replacement, check the following:

Replacement Considerations What to Confirm
Voltage Input Confirm the actual system voltage and select the correct APM-96Q input version
Current Input Check whether existing CTs use 1 A or 5 A secondary output
Auxiliary Power Confirm the available AC/DC supply is compatible with the selected version
Communication Select RS485 Modbus RTU or optional Ethernet Modbus TCP
Harmonic Measurement Confirm whether the project requires 63rd or 127th harmonic measurement
Digital I/O Check the number of required DI, DO, and AO channels
Installation Verify panel cutout, installation depth, and terminal positions
System Integration Check Modbus register mapping, data formats, and communication settings