Elite 500 High-precision TFT display Multifunctional Power Meter

The Elite 500 series is a set of devices with advanced power monitoring capabilities. It can be used for standalone device monitoring and power quality analysis as a part of the building management system (BMS). It can also process industrial controls and SCADA systems.

Contact us

Feature

  • TFT colour display showing vector diagram, bar chart, weekly /monthly energy consumption comparison
  • 17 energy parameter measurement support including net and absolute energy parameters
  • Energy resolution: 7+3-digit, instantaneous parameters: 4+3-digit, high-resolution page for energy measurement
  • Class 0.2S / 0.5S accuracy for energy measurement
  • Configurable favourite parameter on the display page
  • Time synchronisation options through SNTP
  • Power quality features including individual harmonics, THD, sag, swell, voltage unbalance and interruption counter
  • Total demand distortion (TDD) factors and waveform quality indices like K factor and crest factor
  • Positive, negative and zero sequence components
  • Flexible time-of-day tariff, maximum demand / demand support, DST (daylight saving time)
  • Supports PIPO / DIDO, alarm and analogue output module

 

Application

  • Energy transfer measurement and reconciliation
  • Power plants, feeder monitoring, grid substations, wind turbines, renewables, industrial and commercial premises
  • Online monitoring of energy exchange at various interface points
  • Automation and system integration
  • Process and factory automation
  • Retrofit application up to 4000A can be served by using Rogowski coil
  • Different field add-on modules supporting different applications like Modbus, BACnet, Profinet, IEC 61850 protocol support, analogue output and control IOs
  • Various industries like oil and gas, mining, hospitals, malls, datacentres, etc.
  • LV, MV, and HV switchgear

Specification

Conventional Rogowski
Electrical
Connection type LV 3P4W / HV 3P4W / 1CT 3PT / LV 3CT / HV 3P3W / 3CT 2PT / 2CT 2PT / 1P 2W
Measurement voltage range 35 V to 500 V (L-L) max, 20 V to 300 V (L-N) max
Measurement current range 10mA – 6 A (configurable) 5% Ipr -Ipr (Ipr -1000 A or 4000 A)
Starting current range 1mA 1 A for 1000 A / 4 A for 4000 A
Frequency 50 / 60 Hz
Burden Current circuit: < 0.2 VA/phase @ 1A & @ 5A
Voltage circuit: < 0.2 VA/phase
Sampling rate 156 samples / cycle / channel
Accuracy
Active energy Class 0.2S / class 0.5S Class 0.5S
Reactive energy Class 0.5S
Voltage, Current, Power 0.2% for measurement range
Frequency ±0.05 Hz
Power factor ±0.005 (0.5 lag to 0.5 lead)
Maximum withstand Voltage 2 times of nominal voltage value for 1 Sec repeated 10 times at 10 second interval
Maximum withstand current 1.2 times of Ib continuously
Short time over current 20 times Imax for 1 second
Overload (continuous) 1.5 times of Ib, Up to 7.5A (only measurement)
Standards IEC 62052-11, IEC 62053-22, IEC 62053-24, IEC61557-12, IEC 62053-31,

IEC 60529, IEC 61010-1, IEC 61010-2-030, IEC 61326-1, IS14697, CE, UKCA

IEC 61850-6, 7-1, 7-2, 7-3, 7-4, 8-1, (as per edition 1 and 2)
Environmental
Ingress protection IP 54 (front fascia); IP20 (at terminals), IP 65 with gasket (Optional)
Insulation 3.5 kV RMS 50 Hz, 5 seconds
Impulse withstand 6.4 kV
Operating temperature -10°C to + 60°C
Storage temperature -25°C to + 70°C
Temperature coefficient 0.02% / °C 0.1% / °C
Mechanical dimension (H x W x D) 96 x 96 x 57.6 mm (± 0.5 mm), 96 x 96 x 111.5 mm (± 0.5 mm) with module
Weight 365 g 280 g
Software – Two data loggers (16 MB memory):
Primary data logger
Logging of up to 20 energy channels values, with integration
period 5, 15, 30 & 60 minutes
~12500 parameter-days capacity at 30-minute interval
Secondary data logger
Logging of up to 20 instantaneous values with integration period
1, 2, 5, 10, 15 & 30 minutes
~40000 parameter-days capacity at 30-minute interval
– Configurable parameters:
•  8 time-of-use tariffs (TOU), 8 Seasons, 8 day types, DST dates, 6 billing history
•  Logging daily energy snapshots values up to 90 days
•  Alarms and event logging
•  Up to 31st individual harmonic component measurement
•  Up to 63rd total harmonic distortion (THD) measurement
•  K-factor, Crest Factor, TDD, sequence components
•  Power quality features including voltage sag, swell