Schneider PM5560 Power Meter

The Schneider Electric PowerLogic PM5560 (METSEPM5560) is a high-performance, 96 × 96 mm panel-mounted power quality and energy meter. It delivers Class 0.2S active energy accuracy in accordance with IEC 62053-22 and supports harmonic measurement up to the 63rd order for detailed power quality analysis.

Featuring dual-port Ethernet, RS485 Modbus RTU, Modbus TCP, Ethernet/IP, and BACnet communication, the PM5560 also provides 4 digital inputs, 2 digital outputs, 1.1 MB of onboard memory, and 52 configurable alarms. It is designed for WAGES monitoring, multi-tariff metering, and power monitoring in critical industrial facilities, data centers, and commercial buildings.

Contact us

Replace your PM5560 with APM-96Q with selected Ethernet option

Replacing a Schneider PM5560 involves checking the network services it supports alongside its electrical readings. Your meter may connect downstream devices, measure neutral current or serve data through a gateway. Blue Jay APM-96Q with the selected Ethernet option offers a replacement route for defined three-phase power, energy and harmonic monitoring. This page helps you separate those monitoring duties from functions needing additional equipment or supporting evidence, including dual-port networking and IEC 0.2S requirements. Share your network diagram, CT arrangement and required protocols to request a configuration that identifies the meter, accessories and commissioning changes needed for your installation.

Compare specifications of Schneider PM5560 and APM-96Q

Selection point Schneider PM5560 APM-96Q What this means for replacement
Nominal CT input 1 A / 5 A 1 A / 5 A options Order the installed CT secondary; verify measurement and overload limits.
Active-energy accuracy IEC 62053-22 Class 0.2S active energy 0.2; equivalent 0.2S evidence unverified Require configuration-specific 0.2S evidence if the project specifies it.
Neutral-current input 4th CT input for measured neutral current Three-phase current inputs; equivalent 4th CT input unverified Define a separate verified solution where measured neutral current is mandatory.
Ethernet and protocols 2 Ethernet ports; gateway; web server; several protocols Optional Ethernet Modbus TCP; matching port and gateway functions unverified Account for daisy-chain traffic, downstream devices and required protocols.
Voltage measurement Reference 20-400 V L-N; 20-690 V L-L wye 100 / 220 / 380 V ordering options Select voltage rating and connection; include VTs where required.
Control power Reference nominal 100-480 V AC; 125-250 V DC; check tolerances 85-265 V AC/DC standard; 48 V DC or 380 V AC customization published Specify the power version for the actual site supply; confirm its full operating range.
Logs and tariffs 1.1 MB logs; 8 tariffs; 52 alarms 4 rates / 12 segments; 50 SOE; optional logging memory Compare log intervals, retention, tariff logic and exported records.
Opening and depth 96 mm front; product depth 77 mm Manual opening 91 x 91 mm; depth drawing 74 mm Check the actual opening, fixing and cable clearance.

PM5560 replacement configuration

Check and configure the replacement

1 Identify the network job of the PM5560

Show both Ethernet cables, every downstream meter and the protocol used by the supervisory system. A TCP option alone does not reproduce a two-port chain, serial gateway, BACnet or EtherNet/IP.

2 Define current and accuracy requirements

Record all CTs, including any neutral CT, and the required active-energy standard. The APM documents publish 0.2; request applicable evidence for a project requiring IEC 0.2S and a defined solution for direct neutral measurement.

3 Select inputs and records

Match the actual voltage, supply range, opening and I/O circuits. Agree the tariff schedules, log intervals, retention and record formats before selecting firmware and memory options.

4 Commission the complete data path

Install the agreed network equipment and rebuild the point map. Test downstream communication as well as local readings, accumulated energy, alarms and any retained billing or reporting workflow.

Applications for this replacement

Suitable for plant monitoring and control-panel projects where the replacement scope is three-phase electrical data and a defined Modbus connection. A PM5560 acting as a neutral-current meter, network gateway or multi-protocol server needs those duties included in the design.