Key Features
- Three-phase CT-connected energy measurement.
- Active energy accuracy: Class B (Class 1).
- Optional Class 0.5S active energy versions.
- MID-certified versions for billing applications.
- Modbus RTU and M-Bus communication options.
- Import/export energy measurement on selected versions.
- Optional digital inputs and outputs.
Technical Specifications
| Parameters | ABB B24 |
|---|---|
| Product Type | Three-Phase Energy Meter |
| Mounting | DIN Rail |
| Width | 4 DIN modules (70 mm) |
| Voltage System | 3 × 230/400 V AC |
| Current Connection | Indirect CT Connection |
| Maximum Current Input | 6 A |
| Active Energy Accuracy | Class B / Class 1 |
| Optional Accuracy | Class C / Class 0.5S |
| Reactive Energy Accuracy | Class 2 (selected versions) |
| Energy Measurement | Import / Export |
| Communication | IR, optional Modbus RTU / M-Bus |
| Digital Inputs | 2 (optional) |
| Digital Outputs | 2 (optional) |
| Display | LCD |
| Protection | IP20 terminals; IP51 with protective enclosure |
Want the ABB B24 energy Meter Alternative solution?
| Selection point | ABB B24 | DEM-6MC | Replacement implication and source |
| CT measurement | Transformer connected; 1 A rated, 6 A maximum | 1 A or 5 A CT input to order | Select from CT secondary and actual operating current. |
| Active energy | Class 1 or 0.5S by variant | Published Class 0.5S | Check the required standard and supplied evidence. |
| Serial collection | Modbus RTU on specified variants | RS-485 Modbus RTU | Rebuild the device map and scaling. |
| Rail space | 4 DIN modules | 6 modules; drawing width 108 mm | Reserve two additional modules. |
| Voltage and supply | Nominal 230/400 V measuring system | Specify voltage input; auxiliary 85–265 V AC/DC published | Check measuring terminals separately from supply terminals. |
| M-Bus variants | M-Bus on 113 / 353 examples | Native M-Bus not verified | Use a validated integration solution or change the collector. |
| Tariff operation | Silver variants include tariffs and I/O | Four tariffs and programmable periods published | Verify tariff switching method and existing inputs. |
| Billing and environment | MID versions; −40 to +70°C | MID evidence unverified; manual −10 to +55°C | Use for internal monitoring within the selected rating. |