Key Features
- Voltage, current, and frequency measurement.
- Three-phase electrical monitoring.
- 1 A / 5 A CT secondary input.
- Red LED display.
- 96 × 96 mm panel mounting.
- Compact installation depth.
Technical Specifications
| Parameters | ABB M1M 10 |
|---|---|
| Product Type | VAF Meter |
| Mounting | Panel Mount |
| Front Dimensions | 96 × 96 mm |
| Installation Depth | 58 mm overall; approximately 52 mm inside switchboard |
| Voltage Measurement | Yes |
| Current Measurement | Yes |
| Frequency Measurement | Yes |
| Active Power | Not provided |
| Active Energy | Not provided |
| CT Secondary Input | 1 A / 5 A |
| Current Measurement Range | 50 mA–6 A |
| Voltage Input | 40–300 V AC L-N |
| Auxiliary Supply | 80–300 V AC/DC |
| Display | LED |
| Communication | Not available |
| Accuracy – Voltage | ±1.0% |
| Accuracy – Current | ±1.0% |
Aleternative Solution for ABB M1M 10 Power Meter
| Selection point | ABB M1M 10 | APM-96Z | Replacement implication |
| Required readings | Voltage, current and frequency | Voltage, current and frequency | Core local monitoring duties correspond. |
| CT secondary | 1 A or 5 A | 1 A or 5 A to order | Match the installed CT circuit. |
| Additional metering | Power and energy not listed for M1M 10 | Power and active / reactive energy | Useful if the renewed panel needs consumption readings. |
| Communication | No protocol listed for M1M 10 | RS-485 Modbus RTU | Plan new integration only if requested. |
| Supply range | 80–300 V AC/DC | 85–265 V AC/DC published | The original full supply range is not covered. |
| Voltage input | Manual: 80–300 V L-N; older brochure: 40–300 V | Published 18–277 V L-N | Use the installed revision and actual voltage. |
| Mechanical fit | Manual opening 90 +2/0 mm; 96 mm front | Opening 91 +0.8/0 mm; 96 mm front | A nominal 90 mm opening may need enlargement. |
| Depth and temperature | 58 mm in specification; drawing differs; −10 to +60°C | 75 mm drawing; −10 to +55°C | Measure rear space and verify cabinet temperature. |