Key Features
- DIN rail mounting.
- Compatible with 5 A secondary CTs.
- Bidirectional energy measurement.
- Voltage, current, power, energy, and power factor.
- THD monitoring.
- One digital input and one digital output.
- Optional RS485 Modbus RTU.
- Integrated wiring and CT installation error detection.
Technical Specifications
| Parameters | DIRIS A-10 |
|---|---|
| Mounting | DIN Rail |
| Current Input | 5 A CT |
| Voltage Input | 28–289 V AC L-N |
| Frequency | 50 / 60 Hz |
| Active Energy Accuracy | Class 0.5S |
| Reactive Energy Accuracy | Class 2 |
| Energy Measurement | Import / Export |
| Tariffs | Up to 2 |
| Digital Inputs | 1 |
| Digital Outputs | 1 |
| Communication | Optional RS485 |
| Protocol | Modbus RTU |
| Auxiliary Supply | 110–277 V AC |
| Display | Backlit LCD |
| Operating Temperature | -10 to +55°C |
Alternative Solution for Socomec DIRIS A-10
| Selection point | Socomec DIRIS A-10 | APM-4MJ | Replacement implication and source |
| Format | 4 modules; 72 × 90 × 64 mm | DIN; 72 × 110 × 66 mm in manual | Height and cover clearance change despite equal width. |
| CT and energy | 5 A CT; Class 0.5S active energy | 5 A option; manual 0.5S | Check standard-specific evidence and actual load. |
| Communication | 48250400 none; 48250401 RS-485 | Modbus RTU | Update the driver for the communicating original. |
| Auxiliary power | 110–277 V AC / 120–300 V DC | 85–265 V AC/DC standard | Original full range is not covered. |
| Tariff and pulse | Voltage-operated tariff input; optocoupler output | One pulse output or DO in selected manual | Tariff input equivalence is unverified. |
| Select the offered inputs | Verify installed CT or sensor output and measuring voltage | 1 A / 5 A / 100 mA options; select voltage rating | Check polarity, ratio, burden and continuous ratings. |
| Select the offered supply | Verify nameplate and actual supply extremes | 85–265 V AC/DC standard; custom supply requires confirmation | Supply rating is separate from measuring voltage. |