Key Features
- Class 0.2S active energy accuracy.
- Voltage and current harmonics up to 40th order.
- 8 MB internal memory.
- RS485 and Ethernet interfaces.
- Modbus RTU and Modbus TCP/IP.
- Three digital inputs and three digital/pulse outputs.
- Expandable plug-on modules.
- Integrated web server.
Technical Specifications
| Parameters | UMG 96-PA |
|---|---|
| Mounting | Panel Mount |
| Front Dimensions | 96 × 96 mm |
| Auxiliary Supply AC | 90–277 V AC / 24–90 V AC versions |
| Auxiliary Supply DC | 90–250 V DC / 24–90 V DC versions |
| Current Input | 1 A / 5 A CT |
| Active Energy Accuracy | Class 0.2S |
| Harmonic Measurement | Up to 40th |
| Memory | 8 MB |
| Digital Inputs | 3 |
| Digital / Pulse Outputs | 3 |
| Communication | RS485 / Ethernet |
| Protocols | Modbus RTU / Modbus TCP/IP |
| Display | Color Graphic Display |
| Network Types | TN / TT |
Cost-effective solution for Janitza UMG 96-PA
| Selection point | Janitza UMG 96-PA | APM-96J | Replacement implication |
| Active energy | 0.2S at 5 A | Published 0.5S | Not suitable where 0.2S remains mandatory. |
| Harmonics | Through 40th | Through 63rd in selected manual | Monitoring scope can overlap; accuracy is a separate requirement. |
| Local recording | 8 MB listed | SOE; matching interval history unverified | Specify external logging where necessary. |
| Expansion | Plug-on neutral, RCM, temperature and Ethernet functions | Configured I/O and optional TCP | No Janitza module interoperability established. |
| Digital I/O | 3 inputs and 3 digital/pulse outputs | Optional DI / relay / pulse | Check signal type as well as channel count. |
| Select the offered inputs | Verify installed CT or sensor output and measuring voltage | 1 A / 5 A CT; select voltage rating | Check polarity, ratio, burden and continuous ratings. |
| Select the offered supply | Verify nameplate and actual supply extremes | 85–265 V AC/DC standard; low-voltage option requires confirmation | Supply rating is separate from measuring voltage. |