Key Features
- Three-phase multifunction power measurement.
- AC and DC energy metering.
- 1 A / 5 A CT inputs.
- Optional 40 mA HACS inputs.
- DC measurement through external shunt.
- Harmonic analysis up to 40th order.
- Class 0.5 / 0.5S active energy accuracy.
- Optional Class 0.2S calibration.
- RS485, optional Ethernet and Profibus.
- Up to 16 digital and analog I/O.
Technical Specifications
| Parameters | PM130 PLUS |
|---|---|
| Product Type | Multifunction Power Meter |
| Mounting | Panel Mount |
| Current Input | 1 A / 5 A / 40 mA HACS |
| DC Measurement | Via external shunt |
| Voltage Input | 15–828 V AC L-L |
| Frequency | 25 / 50 / 60 / 400 Hz |
| Active Energy Accuracy | Class 0.5 / 0.5S |
| Optional Accuracy | Class 0.2S calibration |
| Harmonics | Up to 40th |
| THD / TDD | Yes |
| K-Factor | Yes |
| Communication | RS485; optional Ethernet / Wi-Fi / Profibus |
| Protocols | Modbus RTU / DNP3.0 / IEC 60870-5-101/104 |
| Digital / Analog I/O | Up to 16, configuration dependent |
| Display | 7-Segment LED with Load Bar |
Cost-effctive Alternative Solution for SATEC PM130 PLUS
| Selection point | Original SATEC | APM-96J | Replacement implication and source |
| Family functions | P basic; E adds energy; EH adds harmonics through 40th | Electrical parameters, energy and 63rd harmonics | Match the actual model, region and firmware. |
| Energy | 0.5S per IEC published | Published 0.5S | Verify standard and operating conditions. |
| Application envelope | AC; DC shunt capability; 25/50/60/400 Hz options | Conventional mains-frequency AC | No DC or 400 Hz substitution established. |
| Protocols | Modbus, DNP3, IEC 60870 options | RTU; TCP / Profibus options | Utility protocol support requires separate evidence or services. |
| Expansion | Multiple I/O modules; up to 16 I/O | Configured optional I/O | Inventory modules and map electrical signal types. |
| Select the offered inputs | Verify installed CT or sensor output and measuring voltage | 1 A / 5 A CT; select voltage rating | Check polarity, ratio, burden and continuous ratings. |
| Select the offered supply | Verify nameplate and actual supply extremes | 85–265 V AC/DC standard; low-voltage option requires confirmation | Supply rating is separate from measuring voltage. |