Features of RCM1000V-75 Residual Current Monitor
- Monitoring of residual currents
- 2 limits for alarm and trip
- Monitoring of current, 2 x under- or overcurrent or windows
- Measuring range 0,003 … 9,999 A
- Setting range 0,010…9,999 A
- Display can be scaled
- Test-button and automatic test every 24 hours
- Input for current transformer STWA3D with monitoring of transformer
- Start-up delay to suppress alarms when switching on
- 4 digits bright LED-display for measured values and programming
- LEDs for alarms, state of relays and units
- Limit, hysteresis, switching delay and switch off delay individually programmable
- Function of relays (nc-, or no-mode) and interlocked switching or autoreset programmable
- Universal supply voltage AC/DC 24-240 V
- Housing for DIN-rail mount, 70 mm wide, mounting height 55 mm
Specification of RCM1000V-75 Residual Current Monitor
- Rated supply voltage: AC/ DC 24V – 240V, < 1,5W, < 5 VA, DC 20,4 – 297 V, AC 20-264 V 50 …500 Hz
- Current relay ( program 2 only): 0,010 A … 9,999 A 10%…25% ,± 2%, ± 3 digit,± 10%, ± 3 digit
- Insulation: 4000 V,AC 300 V III2
- EMC tests: EN 61000-6-3,EN 61000-4-4 ± 4 kV, pulse 5/50 ns, f = 5 kHz, t = 15 ms, T = 300 ms IEC 61000-4-5 ± 2 kV, IEC 61000-4-2 ± 3,8 kV discharge contact, ± 6 kV discharge air
- Operation environment: -20…+65 °C
Dimension of RCM1000V-75 Residual Current Monitor