Key Features
- 96 × 96 mm panel-mounted design.
- Three-phase power analysis.
- Harmonic measurement up to 31st order.
- Four measurement channels.
- RS485 Modbus RTU and BACnet.
- Two digital inputs.
- Two relay outputs.
- Two transistor outputs.
- Power logging.
Technical Specifications
| Parameters | CVM-C11-ITF-IN-485-ICT2 |
|---|---|
| Mounting | Panel Mount |
| Dimensions | 96 × 96 mm |
| Current Input | 1 A / 5 A |
| Voltage Measurement | Three-phase |
| Harmonic Measurement | Up to 31st |
| Measurement Channels | 4 |
| Communication | RS485 |
| Protocols | Modbus RTU / BACnet |
| Digital Inputs | 2 |
| Relay Outputs | 2 |
| Transistor Outputs | 2 |
| Auxiliary Supply | 100–270 V AC/DC |
| Display | Panel Display |
Alternative Solution for Circutor CVM-C11-ITF-IN-485-ICT2
| Selection point | Original Circutor | APM-96J | Replacement implication |
| Exact reference | M58541; ITF; 1 A / 5 A | 1 A / 5 A input to order | Do not apply to MC or FLEX sensor versions. |
| Current channels | 4; includes neutral current | Three-phase; fourth input unverified | Retain separate neutral measurement if mandatory. |
| Harmonics | Through 31st | Through 63rd in selected manual | Validate required accuracy and register data. |
| Protocol | RS-485 Modbus RTU / BACnet | RTU; BACnet unverified | BACnet projects need a qualified conversion. |
| I/O and supply | 2 DI, 2 transistor, 2 relay; 100–270 V AC/DC | Options to specify; standard 85–265 V AC/DC | Match both output technologies and supply extremes. |
| Select the offered inputs | Verify installed CT or sensor output and measuring voltage | 1 A / 5 A CT; select voltage rating | Check polarity, ratio, burden and continuous ratings. |
| Select the offered supply | Verify nameplate and actual supply extremes | 85–265 V AC/DC standard; low-voltage option requires confirmation | Supply rating is separate from measuring voltage. |