Key Features
- Three-phase electrical measurement.
- Harmonics up to 40th order.
- Class 0.5S active energy accuracy.
- Two residual current measurement inputs.
- 256 MB internal memory.
- RS485 and Ethernet.
- Modbus RTU, Modbus TCP/IP, and BACnet.
- Web server and waveform representation.
- Event and energy data recording.
Technical Specifications
| Parameters | UMG 96RM-E |
|---|---|
| Mounting | Panel Mount |
| Front Dimensions | 96 × 96 mm |
| Auxiliary Supply | 90–277 V AC / 90–250 V DC or 24–90 V versions |
| Current Inputs | 4 × 1 A / 5 A CT |
| Residual Current Inputs | 2 |
| Active Energy Accuracy | Class 0.5S |
| Harmonics | Up to 40th |
| Memory | 256 MB |
| Digital I/O | Additional configurable I/O, variant dependent |
| Communication | RS485 / Ethernet |
| Protocols | Modbus RTU / Modbus TCP/IP / BACnet |
| Residual Current Monitoring | Yes |
| Event Resolution | 200 ms high-resolution acquisition |
Janitza UMG 96RM-E Replacement with APM-96Q
| Selection point | Janitza 96RM-E | APM-96Q | Replacement implication and source |
| RCM | 2 residual-current inputs | Equivalent RCM arrangement unverified | Preserve a suitable dedicated monitoring system. |
| Harmonics / energy | 40th; 0.5S at 5 A | 127th; published energy 0.2 | Neither count nor accuracy number proves standards equivalence. |
| History | 256 MB; event and load profiles | Optional 128 MB; SOE | Match intervals, triggers and retrieval rather than memory size. |
| Network | TCP, RTU, BACnet and gateway listed | RTU; optional TCP | BACnet and gateway services need separate evidence. |
| Select the offered inputs | Verify installed CT or sensor output and measuring voltage | 1 A / 5 A CT; select voltage rating | Check polarity, ratio, burden and continuous ratings. |
| Select the offered supply | Verify nameplate and actual supply extremes | 85–265 V AC/DC standard; custom supply requires confirmation | Supply rating is separate from measuring voltage. |