Siemens PAC4200 VS APM-96Q Specification Comparison
| Parameters | Siemens PAC4200 | APM-96Q |
|---|---|---|
| Product Type | Power Monitoring Device | Multifunction Power Analyzer |
| Mounting | Panel Mount | Panel Mount |
| Front Dimensions | 96 × 96 mm | 96 × 96 mm |
| Measurement System | Three-phase | Three-phase |
| Voltage Input | 400 V L-N / 690 V L-L | 100 V / 220 V / 380 V versions |
| Current Input | 5 A CT | 1 A / 5 A CT |
| Voltage Accuracy | Class 0.2 | ±0.1% stated |
| Current Accuracy | Class 0.2 | ±0.1% stated |
| Active Power Accuracy | Class 0.2 | 0.2 stated |
| Reactive Power Accuracy | Class 1.0 | 0.5 stated |
| Active Energy Accuracy | Class 0.2 under IEC 62053-22 (version/standard dependent) | 0.2 stated |
| Reactive Energy Accuracy | Class 2.0 | Class 1.0 |
| Frequency | 45–65 Hz | 40–65 Hz |
| Harmonic Measurement | Voltage: 2nd–64th; current: 3rd–31st | Up to 127th on specified version |
| THD Measurement | Voltage and current | Voltage and current |
| Communication | Ethernet Modbus TCP | RS485 Modbus RTU |
| Optional Communication | RS485 / PROFIBUS / PROFINET | Ethernet Modbus TCP / RTU |
| Digital Inputs | 2 standard | 1–6 optional |
| Digital Outputs | 2 standard | 1–4 optional |
| Analog Outputs | Optional expansion | 1–3 optional |
| Auxiliary Power | 95–240 V AC / 110–340 V DC | 85–265 V AC/DC |
| Optional Auxiliary Power | 22–65 V DC | 48 V DC / 380 V AC customized |
| Display | LCD | 320 × 240 color LCD |
What to Check Before Replacing Siemens PAC4200?
Although APM-96Q offers several comparable measurement and monitoring functions, it should not be treated as a plug-and-play replacement for PAC4200.
Before selecting a replacement, check the following:
| Replacement Considerations | What to Confirm |
|---|---|
| Voltage Input | Confirm the actual system voltage and select the correct APM-96Q input version |
| Current Input | Check whether existing CTs use 1 A or 5 A secondary output |
| Auxiliary Power | Confirm the available AC/DC supply is compatible with the selected version |
| Communication | Select RS485 Modbus RTU or optional Ethernet Modbus TCP |
| Harmonic Measurement | Confirm whether the project requires 63rd or 127th harmonic measurement |
| Digital I/O | Check the number of required DI, DO, and AO channels |
| Installation | Verify panel cutout, installation depth, and terminal positions |
| System Integration | Check Modbus register mapping, data formats, and communication settings |