Key Features
- Three-phase CT energy measurement.
- MID-certified version availability.
- Active and reactive energy measurement.
- Import/export energy.
- Four-tariff management.
- RS485 Modbus RTU.
- Pulse output.
- Self-powered design.
Technical Specifications
| Parameters | COUNTIS E44 |
|---|---|
| Mounting | DIN Rail |
| Network | Three-Phase, 4-Wire |
| Voltage | 3 × 230/400 V AC (MID version) |
| CT Input | 1 A / 5 A |
| Maximum Current | 6 A |
| CT Primary Range | Up to 12,000 A |
| Frequency | 50 Hz ±1 Hz (MID); 50/60 Hz ±1 Hz (non-MID) |
| Energy Measurement | Active / Reactive |
| Direction | Import / Export |
| Tariffs | 4 |
| Communication | RS485 |
| Protocol | Modbus RTU |
| Output | Pulse Output |
| Certification | MID, applicable version |
Alternative Solution for Socomec COUNTIS E44
| Selection point | Socomec COUNTIS E44 | DEM-6MC | Replacement implication |
| Identification | E44 reference 48503066; MID version | DEM-6MC configured for monitoring | Billing equivalence is not established. |
| CT circuit | 1 A / 5 A; three-phase four-wire | 1 A / 5 A to order | Match ratio and circuit before commissioning. |
| Installation | 72 mm width; sealing kit | 108 mm drawing width | Allow extra space and assess any seal implications. |
| Power and data | Self-supplied; RS-485 Modbus | Auxiliary feed required; Modbus RTU | Provide supply and a new device map. |
| Tariff input | 80–276 V AC/DC selects tariff 2 | Dry-contact DI published | A suitable isolated interface or revised control is needed. |
| Select the offered inputs | Verify installed CT or sensor output and measuring voltage | 1 A / 5 A / 100 mA options; select voltage rating | Check polarity, ratio, burden and continuous ratings. |
| Select the offered supply | Verify nameplate and actual supply extremes | 85–265 V AC/DC main specification; confirm supplied range | Supply rating is separate from measuring voltage. |