Key Features
-
- Voltage, current, and frequency measurement.
- Active power measurement.
- Active energy measurement.
- Class 1 active energy accuracy.
- 1 A / 5 A CT input.
- Optional RS485 Modbus RTU communication.
- 96 × 96 mm panel-mounted design.
Technical Specifications
| Parameters | ABB M1M 12 |
|---|---|
| Product Type | Basic Power Meter |
| Mounting | Panel Mount |
| Front Dimensions | 96 × 96 mm |
| Installation Depth | 58 mm overall |
| Voltage Measurement | Yes |
| Current Measurement | Yes |
| Frequency Measurement | Yes |
| Active Power | Yes |
| Active Energy | Yes |
| Reactive Power | Not listed |
| Reactive Energy | Not listed |
| Power Factor | Not listed in range comparison |
| Active Energy Accuracy | 1% |
| Voltage Accuracy | ±1.0% |
| Current Accuracy | ±1.0% |
| CT Secondary Input | 1 A / 5 A |
| Current Measurement Range | 50 mA–6 A |
| Voltage Input | 40–300 V AC L-N |
| Auxiliary Supply | 80–300 V AC/DC |
| Display | LED |
| Communication | Optional RS485 Modbus RTU |
Alternative Solution for ABB M1M 12
| Selection point | ABB M1M 12 | APM-96Z | Replacement implication |
| Working measurements | V, A, Hz, PF, active power and energy | Electrical parameters and energy | These support the main replacement duty. |
| Active energy | Published ±1.0% | Published Class 1 | Different specification expressions; confirm the standard. |
| CT input | 1 A / 5 A; range 50 mA–6 A | 1 A / 5 A rated options | Check low-load performance and operating current. |
| RTU version | M1M 12 Modbus: isolated RS-485, RTU | RS-485 Modbus RTU | Validate serial settings and a new map. |
| Supply | 80–300 V AC/DC | 85–265 V AC/DC published | Verify both ends of the real supply range. |
| Voltage input | Brochure 40–300 V L-N | Published 18–277 V L-N | Check the installed variant and nominal system. |
| Installation | 96 mm format; brochure dimensional data conflict | 96 mm front; opening 91 +0.8/0 mm; depth 75 mm | Measure the installed aperture and rear space. |
| Hours / environment | Operating and load hours; −10 to +60°C | Equivalent hour functions unverified; −10 to +55°C | Check maintenance reporting and cabinet conditions. |