Siemens PAC4220 vs APM-96Q Specification Comparison
| Parameters | Siemens PAC4220 | APM-96Q |
|---|---|---|
| Product Type | Power Monitoring Device | Multifunction Power Analyzer |
| Mounting | Panel Mount | Panel Mount |
| Front Dimensions | 96 × 96 mm | 96 × 96 mm |
| Installation Depth | 56 mm; 78 mm with modules | Confirm mechanical drawing |
| Measurement System | 1P / 2P / 3P; 2-, 3- and 4-wire systems | 3P3W / 3P4W |
| Voltage Input | 57.7/100–400/690 V (IEC) | 100 V / 220 V / 380 V versions |
| Current Input | 1 A / 5 A CT | 1 A / 5 A CT |
| Voltage Accuracy | Class 0.2 | ±0.1% |
| Current Accuracy | Class 0.2 | ±0.1% |
| Active Power Accuracy | Class 0.5; total active power Class 0.2 | ±0.2% |
| Reactive Power Accuracy | Class 0.5 | ±0.5% |
| Active Energy Accuracy | Class 0.2 (IEC 61557-12); Class 0.2S (IEC 62053-22) | Class 0.2 stated |
| Reactive Energy Accuracy | Class 0.5 (IEC 61557-12); Class 0.5S (IEC 62053-24) | Class 1.0 |
| Frequency | 50/60 Hz nominal | 40–65 Hz |
| Harmonic Measurement | 2nd–63rd order | 2nd–127th order |
| THD Measurement | Voltage and current | Voltage and current |
| Communication | 2 × Ethernet, Modbus TCP | RS485 Modbus RTU |
| Optional Communication | RS485 / PROFIBUS / PROFINET | Ethernet Modbus TCP/RTU |
| Digital Inputs | 2 standard; up to 8 optional | Up to 6 optional |
| Digital Outputs | 2 standard; up to 4 optional | Up to 4 optional |
| Analog Outputs | Optional expansion | Up to 3 optional |
| Auxiliary Power | 95–250 V AC / 110–270 V DC | 85–265 V AC/DC |
| Optional Auxiliary Power | 24–48 V DC | 48 V DC / 380 V AC customized |
| Display | 320 × 240 color graphic LCD | 320 × 240 color LCD |