Feature of JZZ-FF Overhead Line Fault Indicator
- Short circuit Fault: Red mechanical flag and three red ultra-bright blinking LEDs.
- Earth-fault: Red mechanical flag and three red ultra-bright blinking LEDs
- Low Battery Warning: Red mechanical flag.
- Parameter Adjust: The parameters can be adjusted by dial switches during production.
- Power Supply: Lithium battery, type AA 2.7Ah/3.6V.
Specification of JZZ-FF Overhead Line Fault Indicator
Subject | Value |
Short-circuit Trip Current (Phase to Phase) | 150A, 300A, 450A, 600A, can be set by dial switch during production |
Trip Current Delay | 40, 80, 120, 200ms, can be set during production |
Indication Unit Reset | 1. Manual by magnet |
2. Time reset: adjustable, 2 minutes, 8h, 24h, 48h, can be set during production | |
3. Auto reset after repower, 30s default, only for permanent fault | |
Protection Class | IP68 |
Internal Type Test | According to IEEE495-2007 |
Operation | -40~+70℃ |
Temperature Range | |
Power Supply | Lithium battery type AA 3.6V/2.7Ah, replaceable |
Battery Life | 10 years |
Weight | Approx. 600g |
Dimensions | Diameter: 93mm |
Height: 128mm | |
Accuracy | 0A~300A ±3A |
300A~800A ±1% | |
Cable Diameter | 6mm~42mm |
Ranges | |
Blinking Frequency | 10 per minute, adjustable |
Max. load/fault Current | 1100A |
Voltage range | 5~14KV. For higher voltage, can be customized |
Current withstand | 31.5KA/4s |