Key Features
- Compact three-module DIN rail installation.
- Three-phase balanced and unbalanced measurement.
- Four-quadrant power measurement.
- Voltage and current THD and harmonics up to 31st order.
- 1 A / 5 A CT versions.
- Optional 250 mA or Rogowski sensor versions.
- RS485 Modbus RTU or BACnet versions.
- One digital input and one transistor output on selected versions.
Technical Specifications
| Parameters | CVM-E3-MINI-ITF-485-IC |
|---|---|
| Mounting | DIN Rail |
| Width | 3 DIN Modules |
| Power Supply | 207–253 V AC |
| Voltage Input | 300 V L-N / 520 V L-L |
| CT Input | 1 A / 5 A |
| Frequency | 45–65 Hz |
| Voltage Accuracy | 0.5% ± 1 digit |
| Current Accuracy | 0.5% ± 1 digit |
| Active Power Accuracy | 0.5% ± 2 digits |
| Active Energy Accuracy | Class 1 / Class 0.5, current dependent |
| Reactive Energy Accuracy | Class 2 |
| Harmonics | Up to 31st |
| Communication | RS485 |
| Protocols | Modbus RTU / BACnet |
| Digital Inputs | 1 |
| Transistor Outputs | 1 |
| Protection | IP31; front IP40 |
Cost-effectice Alternative Solution for CVM-E3-MINI
| Selection point | Circutor CVM-E3-MINI | APM-4MJ | Replacement implication |
| Compared version | M56414 ITF-485-IC; CT 1 A / 5 A | 1 A / 5 A to order | MC 250 mA and WiEth versions require separate assessment. |
| Communication | RTU and BACnet via RS-485 | Modbus RTU | BACnet is not established as a native equivalent. |
| Harmonics | Through 31st | Through 63rd in selected manual | Check output accuracy and available points. |
| Energy | Class 1 below 0.1 In / Class 0.5 above, as published | Manual states 0.5S | Assess low-load behaviour and applicable standards. |
| I/O | 1 digital input and 1 NPN transistor output | One pulse output or DO; equivalent DI unverified | Confirm the input duty before selecting hardware. |
| Power | M56414 listed 207–253 V AC | 85–265 V AC/DC standard | Select from actual supply and required approvals. |
| Select the offered inputs | Verify installed CT or sensor output and measuring voltage | 1 A / 5 A / 100 mA options; select voltage rating | Check polarity, ratio, burden and continuous ratings. |
| Select the offered supply | Verify nameplate and actual supply extremes | 85–265 V AC/DC standard; custom supply requires confirmation | Supply rating is separate from measuring voltage. |