QPPX AC Power Transducer

The AC power transducer is designed to measure a wide range of electrical parameters and produce both analog and digital output signals, making it compatible with various instrumentation and control systems. It offers a total of four-channel output and allows users to configure the settings either through the panel keypad or a PC. This flexibility enables users to choose and set up to four different data points from a maximum of 26 electrical parameters for sampling and analog signal output.

The QPPX programmable transducer is equipped with three digital input channels and features RS485-Modbus communication capabilities. Additionally, the product can monitor galvanically isolated digital input signals and can be programmed using customized SCADA software. Through the RS485 connection, users can access any of the measured parameters.

Contact us
Category:

Features of AC Power Transducer

  • Accuracy 0.5 class
  • 85~265VAC wide voltage AUX for most country
  • With 4 channel output (support max 22 types parameter for analog output)
  • Front panel with 4 keypads for analog parameter configuration, do not need extra configuration software.
  • With RS-485 port for remote electrical data
  • 500ms response time
  • 35mm Din rail mounting
  • Advanced electrical parameter ready optional
  • SOE function optional

Application of AC Power Transducer

 

  • Control panels for instruments
  • Control systems
  • Electrical distribution boards
  • Power transmission systems and generators
  • Supervisory Control and Data Acquisition (SCADA) systems

 

Specification of AC Power Transducer

Electrical Signal Inputs
Nominal input 1 or 5 Amp C.T. connected
110V, 230V, 240V, 400V, 415V ac +/-20%
Power consumption <1 VA voltage
<0.2 VA current
Overload capacity 1.2 times continuous
5sec @ 10 times of rated current
2sec @ 2 times of rated voltage
Frequency range 40~65Hz
Measurement Output
Standard outputs 4~20mA/ 0-20mA programmable
(0~5V / 0~10V optional)
Maximum load <390 Ω (current output)
>10KΩ (voltage output)
Ripple <1% peak to peak
Response time <350ms 0-90%
<500ms 0-99%
Measurement Accuracy
Class 0.2% / 0.5 complying with IEC 60688
Accurate range 0 – 120% I
Frequency influence <0.05% per Hz
Load influence <0.25% of F.S. for specific load range
Auxiliary Supply
Rating 85-265Vac/dc,
Optional 12V, 24V, 48VDC
Consumption <3VA
Galvanic isolation between I/O and AUX
Test voltage 2KV RMS 50Hz for 1 minute
impulse 4KV 1.2/50µsec waveform
Temperature requirements
Operating -10~55℃
Storage -40~70℃, 20 ~ 93%RH ; Noncondensing