Features
- 3-channel Temperature/mV/Ohm Input
- Five-way isolation eliminates potential ground loops between power, Inputand network circuitry
- The input type & measurement range can be programmed setting by ZPconfig software through a separate USB adaptor
- Hot Swappable
- Low Power Loss, Low Temperature Drift, Auto Zero Calibration
- Terminal Block & Rail bus redundant power
- Standard Modbus RTU protocol with high-speed RS-485 communication (up to 115K bps)
- Combine with MWG1 to constitute a remote I/O DAS support both of MODBUS RTU and MODBUS TCP protocols
Specification
◆ Input Signal Type(Programmable By ZPconfig software)
TC: K/E/S/B/R/J/T/N
RTD: PT100/PT200/PT500/PT1000/Cu50
Resistance: 0~400Ω 0~4000Ω
mV: +80mV
Voltage: 0~1V dc
◆Input Channel:3 Channels
◆Input Impedance:≥10MΩ
◆A/D resolution :24 bit
◆Communication:RS485
◆Protocol:Modbus RTU
◆Baud Rate:115200,38400,19200…4800bps (config. by DIP)
◆Address ID:1-31(config. by DIP)
◆RS485Drive Capacity:Max. 64nodes
◆Power Supply:24VDC±10% or AC
◆ Response Time: ≦0.4S
◆ Accuracy:
TC: ≤ 1C°
RTD: ≤ 0.2C°
Resistance: ≤ 0.05% F.S.
mV: ≤+10uV
Voltage: ≤+10mV
◆ Sampling Rate: 9 times/sec.
◆ Digital Output: Single PrecisionFloating-Point
◆Power Loss:1.2W (24VDC)
◆Temperature Drift:0.01%/Celsius degree
◆Operation Temperature:-10~70°C
◆Storage Temperature: -40~80°C
◆ Relative Humidity:5-95% non condensing
◆ 6-way isolation between each channel of input/each channel of output/ communication/power supply:≥1500VAV/1min
◆6-way isolation resistance:≥100Mohm/500V
◆ Calibrating ambient temperature:25±2 °C
◆ EMC:EN1326: 1997+A1:1998+A2:2001+A3:2003
◆Removable plug-in type terminal blocks rated for 12A/250V; AWG #26-12, stranded/solid copper wire
◆Casing/Terminal: IP50/IP20
◆ Weight: 122g
Dimension