SITRANS TH200 Siemens Temperature Transmitter

SITRANS TH200 Siemens Temperature Transmitter is designed to support all common RTDs, thermocouples, resistance and millivolt sensors. Setup is quick and easy with the transmitter modem and downloadable SIPROM T software.

Contact us

Features

  • Compact design
  • Flexible mounting and a center hole allow you to select your preferred type of installation
  • Galvanic isolation
  • Test sockets for multimeters
  • Diagnostics LED (green/red)
  • Sensor monitoring

open circuits and short-circuits

  • Self-monitoring
  • Configuration status stored in EEPROM
  • SIL2 (with order note C20), SIL2/3 (with C23)
  • Expanded diagnostic functions, such as slave pointer, operating hours counter,
  • Special characteristic
  • Electromagnetic compatibility to EN 61326 and NE21

Application

SITRANS TH200 transmitters can be used in all industrial sectors. Due to their compact size they can be installed in the connection head type B (DIN 43729) or larger. The following sensors/signal sources can be connected over their universal input module:

  • Resistance thermometers (2, 3 or 4-wire system)
  • Thermocouples
  • Resistance-based sensors and DC voltage sources

The output signal is a direct current from 4 to 20 mA in accordance with the sensor characteristic.

Transmitters of the “intrinsically safe” type of protection can be installed within potentially explosive atmospheres. The devices meet the directive 2014/34/EU (ATEX) as well as the FM and CSA requirements.

Specification

Input

Resistance thermometer

Measured variable

Temperature

Sensor type

  • According to IEC 60751

Pt25 … Pt1000

  • Acc. to JIS C 1604; a = 0.00392 K-1

Pt25 … Pt1000

  • According to IEC 60751

Ni25 … Ni1000

  • Special type

Via special characteristic (max. 30 points)

Sensor factor

0.25 … 10 (adaptation of the basic type, e.g. Pt100 to version Pt25 … 1000)

Units

°C or °F

Connection

  • Standard connection

1 resistance thermometer (RTD) in 2-wire, 3-wire or 4-wire system

  • Averaging

2 identical resistance thermometers in 2-wire system for generation of average temperature

  • Differentiation

2 identical resistance thermometers (RTD) in 2-wire system (RTD 1 – RTD 2 or RTD 2 – RTD 1)

Connection

  • 2-wire system

Line resistance can be configured ≤100 Ω (loop resistance)

  • 3-wire system

No trim necessary

  • 4-wire system

No trim necessary

Sensor current

≤ 0.45 mA

Response time

≤ 250 ms for 1 sensor with break monitoring

Break monitoring

Always active (cannot be switched off)

Short-circuit monitoring

Can be switched on/off (default value: ON)

Measuring range

Assignable (see “Digital measuring error” table)

Min. measuring span

10 °C (18 °F)

Characteristic curve

Temperature-linear or special characteristic