One Input Four Output Signal Isolator

This series of Signal Isolator use professional MCU and 24-bit high-precision AD for data acquisition, Measuring the DC input signal, while isolated output four-way standard DC signal of 0 ~ 20mA or 0 ~ 5V or 4 ~ 20mA or 1 ~ 5V. It is with high precision, high isolation, low power consumption, low drift, wide temperature range, strong anti-interference ability and so on. The transducer uses a fully isolated design, that is, input, output and power are isolated from each other, eliminating the mutual interference between the signals. This product is widely used in electric power, communication, railway, mining, metallurgy, transportation, instrumentation and other industries because of its ultra-thin housing DIN rail card-mounted structure, plug-in terminal wiring, installation and maintenance convenience.

 

Contact us
Category:

Features

  • It can switch the analog signal output to 0-20mA (0-5V) or 4-20mA (1-5V) output through the internal DIP switch. The four-way output signals are independent of each other.;
  • The internal is used digital adjustment, no potentiometer adjustment technology, the advantages of using the technical: product debugging convenience and product output has no influence from external mechanical vibration, product performance and stability.
  • The use of advanced digital-analog conversion circuit for DA conversion with stability output, low temperature drift.

 

 

Application

  • Signal change & process value scaling.
  • Filtration of noise
  • Protect against EMC
  • Crosstalk elimination
  • Electrostatic filtration
  • Ground loops elimination

 

Specification

* Test conditions: auxiliary power supply: +24 V, room temperature: 25 ℃;

* Input range: 0-20mA/4-20mA/0-5A/0-10V/1-10V/0-500V or custom input type (voltage Max 500V, current Max 5A)

* Output: 0-5V, 1-5V, 0-10V, 2.5±2.5V, 0-20mA, 4-20mA, 10±10mA;

* Power supply: +24VDC (-15%~+20%)

* Accuracy:  class 0.2;

* Load capacity: current output ≤500Ω; voltage output ≥1kΩ;

* Temperature drift: ≤100ppm/℃;

* Isolation voltage: 2500VDC;

* Response time: ≤200 mS;

* Rated power consumption: <3W;

* Output ripple: ≤10mV;

* Frequency response range: none;

* Surge impact immunity:

Power port two-level ±1KV (L-N/2Ω/ integrated wave)

Analog output port three-level ±2KV (L-N/40Ω/integrated wav);

* Impulse immunity: power port ± 2KV, input/output port ± 1KV;

* Input overload capacity:2 times of the measured nominal value(apply one second, repeat 10    times,    interval 10S);

* Weight: 144g, size:L*W*H = 115*96*18mm;

* Operating temperature: -20~70℃; humidity: ≤95% (no dew);

* Storage temperature: -40~+70℃.