Features of Thermistor Motor Protection relay
- UL/CSA and CCC approvals
- The K version is ATEX certified
Application of Thermistor Motor Protection relay
- Control and safety of motors for different types of drives
- Application-specific standard configurations that reduce the amount of time needed to set up and commission relays
- preconfigured systems for industrial and utility distribution
Specification of Thermistor Motor Protection relay
General | XTOD/XTOG | |||
Standards | IEC/EN 60947, GB 14048 | |||
Climatic Proofing | Damp heat, constant, to IEC60068-2-78
Damp heat, cyclic, to IEC60068-2-30 |
|||
Ambient temperature | ||||
Open | °C | -25~55 | ||
Enclosed | °C | -25~40 | ||
Temperature compensation | °C | -5~40 | ||
Weight | kg | 0.15 | ||
Protection type | IP20 | |||
Main contacts |
XTOD/XTOG |
|||
Rated impulse withstand voltage | Uimp | VAC | 6000 | |
Overvoltage category/pollution degree | III/3 | |||
Rated insulation voltage | ||||
AC | Ui | VAC | 690 | |
Rated operational voltage | Ue | VAC | 690 | |
Overload release setting range | A | 0.1-97 | ||
Terminal capacity
Solid |
mm2 |
1 x (1-6) |
||
2 x (1-6) | ||||
Flexible with ferrule | mm2 | 1 x (1-6)
2 x (1-6) |
||
Solid/stranded | AWG | |||
Terminal screw | M4 | |||
Tightening torque | Nm | 1.2 | ||
Auxiliary and control circuits |
XTOD/XTOG |
|||
Rated impulse withstand voltage | Uimp | V | 6000 | |
Overvoltage category/pollution degree | III/3 | |||
Terminal capacity
Solid |
mm2 |
1 x (1-6) |
||
2 x (1-6) | ||||
Flexible with ferrule | mm2 | 1 x (1-6)
2 x (1-6) |
||
Solid/stranded | AWG | |||
Terminal screw | M3.5 | |||
Tightening torque | Nm | 0.8 | ||
Rated insulation voltage | Ui | VAC | 690 | |
Rated operational voltage | Ue | VAC | 690 | |
Conventional thermal current | Ith | A | 10 | |
Rated operational current | ||||
AC-15
120V |
Ie |
A |
6 |
|
220/240V | Ie | A | 3 | |
380V | Ie | A | 1.9 | |
480V | Ie | A | 1.5 | |
500V | Ie | A | 1.4 | |
600V | Ie | A | 1.2 | |
DC-13 | ||||
125V | Ie | A | 0.55 | |
250V | Ie | A | 0.27 |