Feature
- RTD/PTC temperature option
- Password-protected alarm & trip settings
- Ability to detect ground faults on grounded DC systems
- 32-char OLED display
- Earth-leakage metering, setup and programming
- Local LED indication
- Visual Trip, Alarm, CT connection indication
- CT-Loop monitoring
- Alarms when CT is not connected
- Analog output (4-20 mA)
- Connect to DCS. Allows connection to an optional meter (PGA-0520) or control system
- Adjustable time delay
- Adjustable trip delay for quick protection and system coordination
Applications
- Service entrance ground fault protection
- General industrial use
Specifications
- IEEE Device Numbers: AC ground fault (50G/N, 51G/N), DC ground fault (79G), PTC overtemperature (49), RTD temperature (38, 49)
- Supply Voltage: 120/240 Vac/Vdc, 24 Vdc, 48 Vdc/24 Vac
- Trip Level Settings: 30-5,000 mA AC and DC
- Alarm Level Settings: 30-5,000 mA AC and DC
- Trip Delay: 0.05-2 s
- Output Contacts: 3 Form C (programmable)
- Contact Operating Mode: Fail-safe & non-fail-safe
- Reset: Front panel and remote
- Freq. Response, CT1: 0-90 Hz
- Freq. Response, CT2: 20-6,000, 190-6,000, 20-90, 20-3,000 Hz; selectable
- Current Transformer: EFCT-x series
- CT Detection: Open & short detection
- Terminals: Plug-in, wire clamping, 24 to 12 AWG (0.2-2.5 mm2)
- Communications: EtherNet/IP™, DeviceNet™, Profibus®, Modbus® TCP (optional)
- Analog Output: 4-20 mA (selectable 0-5 A or 0-100% trip-level setting)
- Conformal Coating: Standard feature
- Dimensions: H 48 mm (1.9”); W 96 mm (3.8”); D 129 mm (5.0”)
- Approvals: UL Listed (E340889), CSA, RCM (Australia), CE
- Warranty: 5 years
- Mounting: Panel; Surface and DIN (with optional AC700-SMK)