The arc protection BSSDZ-03 is for high-speed selective light detection. The device has passed the certification procedure of PJSC Rosseti and is included in the list of equipment, materials, and systems recommended for use at the facilities of SDEs of PJSC Rosseti. Designed for operation in indoor and outdoor switchgear with a voltage of 6, 10, and 35 kV in order to detect short circuits accompanied by an open electric arc, to exclude or minimize damage caused by an electric arc.

Contact us
Category:

Features

  • Interface for connection to the substation bus using the MMS protocol;
  • Interface for connecting to the process bus using the GOOSE protocol;
  • 4 fiber-optic sensors of a point type for registration of an arc discharge with a function of continuous monitoring of the performance of each sensor;
  • The possibility of using a loop-type sensor instead of a point one;
  • Decommissioning of any number of sensors;
  • Protection against false alarms when illuminated by a 60 W incandescent lamp from a distance of at least 15 cm and from sunlight;

 

Applications

  • Reduce the harm of arc light to human body;
  • Reduce damage to equipment caused by arc short-circuit faults;
  • Avoid transformer damage caused by bus failure;
  • Protect the dc system in the station;
  • Ensure the stable operation of power substations;
  • Thermal power plant electrical section switchgear;
  • Wind farm and photovoltaic station switchgear;
  • Large municipal engineering project;

 

Specification

  • Supply voltage – 24 V DC, 1 A;
  • Operating temperature range – from – 35 C to + 65 C;
  • WATER operation threshold – no more than 0.5 mw/cm;
  • Response time – no more than 2 ms;
  • Up to 12 channels for connecting fiber-optic sensors of point or loop type;
  • Up to 8 freely programmable electromechanical output relays for the organization of trip signals and inhibitions of automatic reclosure and automatic reclosure;
  • Connection of up to 100 expansion units to increase the number of sensors and output signals from the OVOD-L arc protection device line via the CAN bus;
  • 4 analog inputs for measuring 3 phase currents (A,B,C) and zero sequence 3Io.
  • Main characteristics of analog inputs:
  • Rated current – 1/5 A;
  • Range of measured effective values of phase currents – 0.5…50