Schneider LC1D09P7 IEC AC contactor

The Schneider LC1D09P7 TeSys D AC contactors are engineered to seamlessly integrate with control systems. They are useful for producing motor starters for practically any kind of application. For resistive loads up to 200 amps and inductive motor applications up to 150 full-load amps, TeSys D contactors are offered in 13 contactor grades.

You have two options for mounting this 9A inductive 3-pole IEC contactor: directly into a panel or on a DIN rail. For global acceptance, contactors are rated for both horsepower and kilowatts of motor power. Three-phase contactor ratings are as follows: 20 HP at 200-208 VAC, 25 HP at 240 VAC, 60 HP at 480 VAC, and 60 HP at 600 VAC.

Contact us
Category:

Features of Schneider LC1D09P7

  • long service life, able to withstand high voltage and high current loads.
  • Elevated sensitivity and rapid response time can guarantee precise circuit functioning.
  • It is easy to install, has a straightforward operation, and can be adjusted to fit different circuit needs.
  • It is lightweight, compact, and requires minimal room.
  • It can increase the stability of the circuit and endure high, low, and humid environments.
  • Effective sealing can stop extraneous objects from getting into the
  • High power, appropriate for high-power circuit control.
  • Minimal vibration, minimal noise, steady operation.
  • Possesses strong durability

Applications of Schneider LC1D09P7

  • Frequently employed in large-scale air conditioning system control.
  • Lighting system to operate the light switch.
  • Used in refrigeration systems for compressor control.
  • The motor can perform standard start-stop and reverse operations under motor control.
  • Used to regulate the connecting and disconnecting of capacitors in power capacitor banks
  • Utilized in industrial manufacturing lines’ automation control

Specification of Contactor LC1D09P7

 
Motor power kW 2.2 kW 220…230 V AC 50/60 Hz AC-3)
4 kW 380…400 V AC 50/60 Hz AC-3)
4 kW 415…440 V AC 50/60 Hz AC-3)
5.5 kW 500 V AC 50/60 Hz AC-3)
5.5 kW 660…690 V AC 50/60 Hz AC-3)
2.2 kW 400 V AC 50/60 Hz AC-4)
2.2 kW 220…230 V AC 50/60 Hz AC-3e)
4 kW 380…400 V AC 50/60 Hz AC-3e)
4 kW 415…440 V AC 50/60 Hz AC-3e)
5.5 kW 500 V AC 50/60 Hz AC-3e)
5.5 kW 660…690 V AC 50/60 Hz AC-3e)
Maximum Horse Power Rating 1 hp 230/240 V at AC 50/60 Hz for 1 phase
2 hp 200/208 V at AC 50/60 Hz for 3 phase
2 hp 230/240 V at AC 50/60 Hz for 3 phase
5 hp 460/480 V at AC 50/60 Hz for 3 phase
7.5 hp 575/600 V at AC 50/60 Hz for 3 phase
0.33 hp 115 V at AC 50/60 Hz for 1 phase
Compatibility code LC1D
Pole contact composition 3 NO
Contact compatibility M2
Protective cover With
[Ith] conventional free air thermal current 25 A 140 °F (60 °C) power circuit
10 A 140 °F (60 °C) signalling circuit
Irms rated making capacity 250 A 440 V power circuit IEC 60947
140 A AC signalling circuit IEC 60947-5-1
250 A DC signalling circuit IEC 60947-5-1
Rated breaking capacity 250 A 440 V power circuit IEC 60947
[Icw] rated short-time withstand current 105 A 104 °F (40 °C) – 10 s power circuit
210 A 104 °F (40 °C) – 1 s power circuit
30 A 104 °F (40 °C) – 10 min power circuit
61 A 104 °F (40 °C) – 1 min power circuit
100 A – 1 s signalling circuit
120 A – 500 ms signalling circuit
140 A – 100 ms signalling circuit
Associated fuse rating 10 A gG signalling circuit IEC 60947-5-1
25 A gG <= 690 V type 1 power circuit
20 A gG <= 690 V type 2 power circuit
Average impedance 2.5 mOhm – Ith 25 A 50 Hz power circuit
Power dissipation per pole 1.56 W AC-1
0.2 W AC-3
0.2 W AC-3e
[Ui] rated insulation voltage Power circuit 690 V IEC 60947-4-1
Power circuit 600 V CSA
Power circuit 600 V UL
Signalling circuit 690 V IEC 60947-1
Signalling circuit 600 V CSA
Signalling circuit 600 V UL
Overvoltage category III
Pollution degree 3
[Uimp] rated impulse withstand voltage 6 kV IEC 60947
Safety reliability level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability 15 Mcycles
Electrical durability 0.6 Mcycles 25 A AC-1 <= 440 V
2 Mcycles 9 A AC-3 <= 440 V
2 Mcycles 9 A AC-3e <= 440 V
Control circuit type AC 50/60 Hz standard
Coil technology Without built-in suppressor module
Control circuit voltage limits 0.3…0.6 Uc -40…158 °F (-40…70 °C) drop-out AC 50/60 Hz
0.8…1.1 Uc -40…140 °F (-40…60 °C) operational AC 50 Hz
0.85…1.1 Uc -40…140 °F (-40…60 °C) operational AC 60 Hz
1…1.1 Uc 140…158 °F (60…70 °C) operational AC 50/60 Hz
Inrush power in VA 70 VA 60 Hz 0.75 68 °F (20 °C))
70 VA 50 Hz 0.75 68 °F (20 °C))
Hold-in power consumption in VA 7.5 VA 60 Hz 0.3 68 °F (20 °C))
7 VA 50 Hz 0.3 68 °F (20 °C))
Heat dissipation 2…3 W 50/60 Hz
Operating time 12…22 ms closing
4…19 ms opening
Maximum operating rate 3600 cyc/h 140 °F (60 °C)
Connections – terminals Power circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²) flexible without cable end
Power circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²) flexible without cable end
Power circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²) flexible with cable end
Power circuit screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²) flexible with cable end
Power circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²) solid without cable end
Power circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²) solid without cable end
Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²) flexible without cable end
Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²) flexible without cable end
Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²) flexible with cable end
Control circuit screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²) flexible with cable end
Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²) solid without cable end
Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²) solid without cable end
Tightening torque Power circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm
Power circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals pozidriv No 2
Power circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals pozidriv No 2
auxiliary contact composition 1 NO + 1 NC
Auxiliary contacts type Mechanically linked 1 NO + 1 NC IEC 60947-5-1
Mirror contact 1 NC IEC 60947-4-1
Signalling circuit frequency 25…400 Hz
Minimum switching voltage 17 V signalling circuit
Minimum switching current 5 mA signalling circuit
Insulation resistance > 10 MOhm signalling circuit
Non-overlap time 1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
Mounting Support Rail
Plate