ETCR3000+ 0.01ohm~2000ohm 4 Wires Clamp Grounding Resistance Tester Clamp Meter

ETCR3000+ Digital Earth Resistance Tester specially designed and manufactured for the field measurement of ground resistance, adopts digital and micro-processing technology, 3 wire or 2 wire method to measure ground resistance, with unique calibration function for wire resistance, anti-interference ability and environmental adaptability, to ensure the long-term measurement of high precision, high stability and reliability.

Contact us

Feature of ETCR3000+

  • Earth Resistance Range: 0.010Q~2000Q
  • Earth Voltage Range: OV~600V AC
  • Accuracy: +2%rdg+3dgt
  • Measurement Method: Rated current change-pole method/Average value rectification
  • Power Supply: DC 9V(Alkaline dry battery LR14 1.5V 6 PCS )

Specification of ETCR3000+

Power Supply
DC9V, R6 AAdry batteryX6PCS
Measurement Method
Earth resistance: rated current change-pole method, test current 20mA Max; Voltage to earth: average value rectification
 

Grounding Resistance

Range:0.10 Ω~2000 Ω
Resolution:0.01Ω
Accuracy:±2%rdg±3dgt
 

Grounding Current

Range: 0mA~ 100A AC
Resolution: 1mA
Accuracy: ±2%rdg±3dgt
 

Grounding Voltage

Range:0 ~ 200V AC
Resolution:1V
Accuracy:±2%rdg±3dgt
Display LCD
LCD:58mmX46mm
Tester Dimension
160mm(L)×100mm(W)×66mm(H)
WVeight
Host: about470g; Current clamp: about 190g; total weight: about 2125g (include accessories)
Test Indicator
TESTING indicator lighting, indicate that grounding ressitance is testing
Auxiliary Grounding Indicator
R P(s)R C(H) OK indicator lighting, indicates that the auxiliary grounding electrode is qualified and the testresult is accurate.Otherwise, please re-select the auxiliary grounding point
Measurement Time
Earth resistance: 15 seconds/time;Voltage to earth : 2 times/second; Current: 2times/s
Auxiliary Grounding Rod
2PCS:φ10mm×250mm
Test Wires
Red 15m, yellow 10m, green 5m, red 1.5m (total 4 pcs wires)
Line Resistance Verification
Avoid errors caused by the test line not fully inserted into the instrument interface or poor contact or the user replaces the lengthened test line, ensure grounding resistance measurement more accurate
Auto Shutdown
3 Minutes after power on, will automatic shutdown without any operation..
Battery Voltage
While battery voltage decreases to around 7.2VV, will display low battery voltage symbol“ ”, and remind to replace the battery
Overload Protection
Earth resistance: between each interfaces of E-P,E-C, AC 280V/3 seconds
Electromagnetic Property
IEC61010-4-3, wireless frequency electromagnetic field≤1V/m
Working Current
Backlight:56mA Max; Standby: 20mA Max(Backlight close); Measurement:200mA Max(Backlight close)
Accessories
Tester:1PCS; Current sensor: 1PCS; Grounding rod: 2PCS; Test line:3PCS; Simple test line: 1PCS; Tester bag:1PC