Feature of ETCR3200
- ETCR3200 Double Clamp Grounding Resistance Tester is specially designed for the measurement of earth resistance, soil resistivity, earth voltage, leakage current of the grounding line, AC, DC resistance.
- ETCR3200 Double Clamp Grounding Resistance Tester is composed of the host machine, monitoring software, testing wires, auxiliary ground pillars, communication wires and others.
- The large LCD of host machine is with blue backlight and bar graph indicating that can be seen clearly.
- ETCR3200 Double Clamp Earth Resistance Meter can flexibly and precisely measure the value of grounding resistance in every complicated situation like single point grounding, and grounding mesh; it does not need to disconnect any parallel connection pole when measuring parallel-grounding, and massively improve the convenience when measuring.
- At the same time it can store 2000 sets of data, fulfilling historical inquiry and online real-time monitoring through monitoring software, dynamic display, and alarm indicator, auto-shut down and with the functions like historical data access, reading, preservation, report forms, printing and so on.
Specification of ETCR3200
Power Supply | DC 9V Alkaline dry cell LR14 1.5V*6PCS, continues standby 300 hours |
LCD Size | 124mm x 67mm(with backlight) |
Range | Selection measurement method :0.01Ω – 3000Ω | Double clamp measurement method :0.01Ω – 100Ω | Soil Resistivity :0.01Ωm – 9000KΩ | DC Resistance:0.01Ω – 30.00kΩ | Earth Voltage:0.1V -100.0V | AC Current:0.01mA -600A |
Resolution | Resistance:0.01Ω | Soil Resistivity :0.01Ωm | Current:0.01mA | Voltage:0.1V |
Max Accuracy | ±2%rdg±3dgt |
Data Storage | 2000 groups |
Data Upload | RS232 interface, storage data can be uploaded to computer, saved or printed. |
Automatic Shut Down | Automatically shut down after 15 minutes start up |
Power Consumption | Turn on the backlight: 45mA Max | Turn off the backlight : 25mA Max | Measurement: 100mA Max(Backlight shut off) |
Working Temperature & Humidity | -10℃-40℃, below 80%rh |
Storage temperature & humidity | -20℃-60℃, below 70%rh |
Clamp Caliber | Φ50mm |
Measuring Method | 2/3/4 pole measurement method: Change-pole method, measurement current 20mA Max | Selection measurement method: Change-pole method, measurement current 20mA Max | Soil Resistivity: 4-pole measurement (Wenner method) | AC current: Mutual inductance method(clamp) | Earth Voltage: Average rectification(between P(S)-ES) |
Test Frequency | 128Hz/111Hz/105Hz/94Hz(AFC) |
Data Model | Average value,maximum,minimum value |
line resistance check | Automatic calibration |
Measuring Rate | AC current: about 0.5 times/second | Earth Voltage: about 0.5 times/second | Earth resistance,soil resistivity: about 5 seconds/time |
Measuring Times | Over 5000 times (Short-circuit test, interval time should be at least 30seconds) |
Short-circuit Test Current | AC 20mA max |
Open-circuit Test Voltage | AC 40V max |
Test Voltage Wave | Sine wave |
Electrode Distance Range | 1m-100m |
Line Voltage | Measurement below AC 600V |
Data Hold | Data hold function: “HOLD” symbol display |
Data Access | Data read function: “READ” symbol display |
Overflow Display | Exceed measuring range overflow function: “OL” symbol display |
Auxiliary Grounding Test | With auxiliary grounding resistance test function, 0.00KΩ-30kΩ(100R+rC<50kΩ, 100R+rP<50kΩ) |
Interference Test | Automatic identification of interference signals, “NOISE” symbol indication when the interference voltage is higher than 5V |
Alarm Function | Measuring value exceeds alarm setting value, will “Toot-toot-toot” alarm hint |
Battery Voltage | While battery voltage decreases to around 7.5V, will display battery voltage low symbol“ ”, and reminding to replace the battery |
Overload Protection | Measure earth resistance: between each interfaces of E-P、E-E- C, AC 280V/3 seconds |
Insulation Resistance | Over 20MΩ(between circuit and outside shell is 500V) |
Withstand Voltage | AC 3700V/rms. (Between circuit and outside shell) |
Electromagnetic Features | IEC61010- 4-3,Wireless frequency electromagnetic field ≤1 V/m |
Safety Standard | IEC61010-1(CAT Ⅲ 300V、CAT IV 150V、Pollution 2) | IEC61010-031 | IEC61557-1(Earth resistance) | IEC61557-5(Soil resistivity) | JJG 366-2004(Grounding resistance meter) |
Weight | 1653g |
Meter Dimension | 215mm(L)×178mm(W)×83mm(H) |