Feature of SIMOCODE pro 3UF7
- Inverse-time delayed electronic overload protection (CLASS 5E to 40E)
- Thermistor motor protection
- Phase failure/asymmetry protection
- Stall protection
- Monitoring of adjustable limit values for the motor current
- Voltage and power monitoring
- Monitoring of the power factor φ (motor idling/load shedding)
- Ground-fault monitoring
- Temperature monitoring, e.g. via Pt100/Pt1000
- Monitoring of operating hours, downtime and number of starts etc.
Application of SIMOCODE pro 3UF7
SIMOCODE pro is often used for automated processes where plant downtimes are very expensive (e.g. chemical, oil/gas, water/wastewater, steel or cement industries) and where it is important to prevent them using detailed operational, service and diagnostics data and to localize faults very quickly when they occur.
SIMOCODE pro is modular and space-saving and suited especially for operation in motor control centers (MCCs) in the process industry and for power plant technology.
- Protection and control of motors in hazardous areas for types of protection EEx e/d according to ATEX Directive 2014/34/EU
- With heavy starting (paper, cement, metal, and water industries)
- In high-availability plants (chemical, oil, raw material processing industries, power plants)
- Dry-running protection of centrifugal pumps based on active power monitoring for the type of protection Ex b
Specification of SIMOCODE pro 3UF7
Electromagnetic compatibility | |
EMC emitted interference according to IEC 60947-1 | class A |
EMC immunity according to IEC 60947-1 | corresponds to degree of severity 3 |
conducted interference | |
● due to burst according to IEC 61000-4-4 | 2 kV (power ports) / 1 kV (signal ports) |
● due to conductor-earth surge according to IEC 61000-4-5 | 2 kV |
● due to conductor-conductor surge according to IEC 61000-4-5 | 1 kV |
● due to high-frequency radiation according to IEC 61000-4-6 | 10 V |
field-based interference according to IEC 61000-4-3 | 10 V/m |
electrostatic discharge according to IEC 61000-4-2 | 6 kV contact discharge / 8 kV air discharge |
conducted HF interference emissions according to CISPR11 | corresponds to degree of severity A |
field-bound HF interference emission according to CISPR11 | corresponds to degree of severity A |
Inputs/ Outputs | |
product function | |
● parameterizable inputs | Yes |
● parameterizable outputs | Yes |
number of inputs | 4 |
● for thermistor connection | 1 |
number of digital inputs with a common reference potential | 4 |
digital input version | |
● type 1 acc. to IEC 61131 | Yes |
input voltage at digital input at DC rated value | 24 V |
number of outputs | 2 |
number of semiconductor outputs | 0 |
number of outputs as contact-affected switching element | 2 |
switching behavior | monostable |
type of relay outputs | Monostable |
wire length for digital signals maximum | 300 m |
wire length for thermistor connection | |
● with conductor cross-section = 0.5 mm² maximum | 50 m |
● with conductor cross-section = 1.5 mm² maximum | 150 m |
● with conductor cross-section = 2.5 mm² maximum | 250 m |
Protective and monitoring functions | |
product function | |
● asymmetry detection | Yes |
● blocking current evaluation | Yes |
● power factor monitoring | No |
● ground fault detection | Yes |
● phase failure detection | Yes |
● phase sequence recognition | No |
● voltage detection | No |
● monitoring of number of start operations | Yes |
● overvoltage detection | No |
● overcurrent detection 1 phase | Yes |
● undervoltage detection | No |
● undercurrent detection 1 phase | Yes |
● active power monitoring | No |
product function | |
● current detection | Yes |
● overload protection | Yes |
● evaluation of thermistor motor protection | Yes |
total cold resistance number of sensors in series maximum | 1.5 kΩ |
response value of thermoresistor | 3 400 … 3 800 Ω |
● of the short-circuit control | 9 Ω |
release value of thermoresistor | 1 500 … 1 650 Ω |
Motor control functions | |
product function | |
● parameterizable overload relay | Yes |
● circuit breaker control | Yes |
● direct start | Yes |
● reverse starting | Yes |
● star-delta circuit | Yes |
● star-delta reversing circuit | No |
● Dahlander circuit | No |
● Dahlander reversing circuit | No |
● pole-changing switch circuit | No |
● pole-changing switch reversing circuit | No |
● slide control | No |
● valve control | No |
Communication/ Protocol | |
protocol is supported | |
● PROFIBUS DP protocol | Yes |
● PROFINET IO protocol | No |
● PROFIsafe protocol | No |
● Modbus RTU | No |
● EtherNet/IP | No |
● OPC UA Server | No |
● LLDP | No |
● Address Resolution Protocol (ARP) | No |
● SNMP | No |
● HTTPS | No |
● NTP | No |
● Media Redundancy Protocol (MRP) | No |
number of interfaces | |
● according to PROFINET | 0 |
● according to PROFIBUS | 1 |
● according to Ethernet/IP | 0 |
product function | |
● web server | No |
● shared device | No |
● at the Ethernet interface Autocrossover | No |
● at the Ethernet interface Autonegotiation | No |
● at the Ethernet interface Autosensing | No |
● is supported Device Level Ring (DLR) | No |
● is supported PROFINET system redundancy (S2) | No |
● supports PROFIenergy measured values | No |
● supports PROFIenergy shutdown | No |
transfer rate maximum | 1.5 Mbit/s |
identification & maintenance function | |
● I&M0 – device-specific information | Yes |
● I&M1 – higher level designation/location designation | Yes |
● I&M2 – installation date | Yes |
● I&M3 – comment | Yes |
type of electrical connection of the communication interface | Screw-type terminal (1.5 Mbit) |
Installation/ mounting/ dimensions | |
mounting position | any |
fastening method | screw and snap-on mounting |
height | 100 mm |
width | 22.5 mm |
depth | 124.5 mm |
required spacing | |
● top | 40 mm |
● bottom | 40 mm |
● left | 0 mm |
● right | 0 mm |
Connections/ Terminals | |
product component removable terminal for auxiliary and control circuit | Yes |
type of connectable conductor cross-sections | |
● solid | 1x (0.5 … 2.5 mm²), 2x ( 0.5 … 1.5 mm²) |
● finely stranded with core end processing | 1x (0.5 … 2.5 mm²), 2x (0.5 … 1 mm²) |
● for AWG cables solid | 1x (20 … 14), 2x (20 … 16) |
tightening torque with screw-type terminals | 0.6 … 0.8 N·m |
tightening torque [lbf·in] with screw-type terminals | 5.2 … 7 lbf·in |
type of connectable conductor cross-sections for PROFIBUS wire | 2x 0.34 mm², AWG 22 |
Ambient conditions | |
installation altitude at height above sea level | |
● 1 maximum | 2 000 m |
● 2 maximum | 3 000 m; max. +50 °C (no protective separation) |
● 3 maximum | 4 000 m; max. +40 °C (no protective separation) |
ambient temperature | |
● during operation | -25 … +50 °C |
● during storage | -40 … +80 °C |
● during transport | -40 … +80 °C |
environmental category | |
● during operation according to IEC 60721 | 3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6 |
● during storage according to IEC 60721 | 1K6 (only occasional condensation), 1C2 (no salt mist), 1S2 (sand must not get inside the devices), 1M4 |
● during transport according to IEC 60721 | 2K2, 2C1, 2S1, 2M2 |
relative humidity | |
● during operation | 10 … 95 % |
contact rating of auxiliary contacts according to UL | B300 / R300 |
Short-circuit protection | |
design of short-circuit protection per output | Fuse links: gG 6 A, quick-response 10 A (IEC 60947-5-1), miniature circuit-breaker C char.: 1.6 A (IEC 60947-5-1) or 6 A (I_K < 500 A) |
Electrical Safety | |
touch protection against electrical shock | finger-safe |
ATEX | |
certificate of suitability | |
● acc. to Equipment and Protective System Intended for Use in Potentially Explosive Atmospheres Regulations 2016 (S.I. 2016 No.1107) | ITS21UKEX0464, ITS21UKEX0455X |
Galvanic isolation | |
(electrically) protective separation according to IEC 60947-1 | All circuits with protective separation (double creepage paths and clearances), the information in the “Protective Separation” test report, No. A0258, must be observed (link see further information) |
Control circuit/ Control | |
product function soft starter control | Yes |
type of voltage of the control supply voltage | AC/DC |
control supply voltage at AC | |
● at 50 Hz rated value | 110 … 240 V |
● at 60 Hz rated value | 110 … 240 V |
control supply voltage frequency | |
● 1 rated value | 50 Hz |
● 2 rated value | 60 Hz |
relative symmetrical tolerance of the control supply voltage frequency | 5 % |
control supply voltage at DC rated value | |
● | 110 … 240 V |
operating range factor control supply voltage rated value at DC | |
● initial value | 0.85 |
● full-scale value | 1.1 |
operating range factor control supply voltage rated value at AC at 50 Hz | |
● initial value | 0.85 |
● full-scale value | 1.1 |
operating range factor control supply voltage rated value at AC at 60 Hz | |
● initial value | 0.85 |
● full-scale value | 1.1 |
inrush current peak | |
● at 240 V | 10 A |
duration of inrush current peak | |
● at 240 V | 1 ms |