900ELR Selec Earth Leakage Relay

Contact us

Feature

  • Digital earth leakage detection for 1 and 3-phase systems
  • 2 X 1 C / O (SPDT) Relay output
  • Supply voltage of 230 VAC±15% & 110V AC±15%
  • DIN rail mounting
  • CE Certified

Specifications

Measuring Parameter Leakage Current Monitoring in 3Ø & 1Ø Systems
Electrical Connection 1Ø-2W, 3Ø-3W, 3Ø-4W
Display 3 Digits Liquid Crystal Display With Backlight.
Trip Setting 30mA – 30A
Time Ranges Power ON Delay: 0.5-99.9sec,
Trip Time Delay: 0-99.9sec,
Recovery Time Delay: 0-99.9sec
Accuracy Current: ± 5% of setting, Recovery Time,
Trip Delay,
Power ON Delay: ± 5% of Setting + 100
Output Contact 2 X 1 C / O (SPDT)
Output Rating NC:3A @ 250V AC, NO:5A @ 250V AC
Supply Voltage 230V AC & 110V AC
Size 35mm
Mounting Type DIN Rail Mount
Certification CE