Feature
- Soft-start current can reduce the AC input impact effectively
- With short-circuit and overload protection
- 100% full-load burn-in test
- Installed with EMI filter, minimum wave
Specification
Model | DR-75-24 | |
OUTPUT | DC VOLTAGE | 24V |
RATED CURRENT | 3.125A | |
CURRENT RANGE | 0 ~ 3.125A | |
RATED POWER | 75W | |
RIPPLE&NOISE(Max) | 100mVp-p | |
VOLTAGE ADJ.RANGE | 24 ~ 30V | |
VOLTAGE TOLERANCE | ±1.0% | |
LINE REGULATION | ±0.5% | |
LOAD REGULATION | ±1.0% | |
SETUP,RISE TIME | 500ms、30ms/230VAC 1000ms,30ms/115VAC(full load) | |
INPUT | VOLTAGE RANGE | 85~264VAC , 120~370VD |
FREQUENCY RANGE | 47~63Hz | |
EFFICIENCY(Typ.) | 0.85 | |
AC CURRENT(Typ.) | 0.7A/115VAC 40A/230VAC | |
INRUSH CURRENT(Typ.) | COLDSTART: 60A/230V | |
LEAKAGE CURRENT | <1mA/240VAC | |
PROTECTION | OVER LOAD |
105 ~ 150% rated output power |
Protection tye:Hiccup mode,recovers automatically after fault condition is removed | ||
OVER VOLTAGE |
28.4~32.4V | |
Protection type : Shut down o/p voltage, re-power on to recover | ||
ENVIRONMENT | WORKING TEMP | -10 ~ +60°C |
WORKING HUMIDITY | 20~90%RH | |
STORAGETEMP.,HUMIDITY | -20 ~ +85°C, 20 ~ 90% RH | |
VIBRATION | Component : 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes | |
SAFETY | SAFETY STANDARDS | CE,GB4943.1safety standard |
WITHSTAND VOLTAGE | I/P-O/P:1.5KVAC 1minute I/P-FG:1.5KVAC 1minute O/P-PG:0.5KVAC 1minute | |
ISOLATION RESISTANCE | I/P-O/P, I/P-FG, O/P-FG:100MOhms/500VDC | |
EMC EMISSION | EN61000-3-2:2014/EN61000-3-3:2013 | |
EMC IMMUNITY | EN 55032:2015/EN55035:2017/60950-1 | |
OTHERS | MTBF | ≥327.9K hrs MIL-HDBK-217F(25°C) |
DIMENSION | 100*55.5*125.2mm |