Feature
- Resistance monitoring. The product can monitor the insulation resistance of the positive and negative poles of the DC system to the ground. When the insulation resistance is lower than the set warning and alarm values, it can send out warning and alarm signals.
- Voltage monitoring. The product can monitor the voltage between the positive and negative poles of the DC system and the voltage between the positive and negative poles with respect to ground. The measurement range is 0~1000V.
- Current monitoring function. The product can monitor the current of DC system, only the AIM-D100-CAI model has this function.
- LED indication. The product panel has operation, communication, and fault LED indicators to display product status.
- Communication networking function. The product has RS485 interface and adopts Modbus-RTU protocol for data exchange.
- Metal casing. The product adopts a metal shell and can be wall-mounted or installed using accessory rails.
- Plug-in terminals. The product adopts plug-in terminal wiring, which is convenient for wiring and installation.
Specification
Technical Parameter | Technical Specifications | |
Auxiliary power | DC 9~36V | |
Maximum power consumption | ≤6W | |
Voltage monitoring | Voltage range | DC 0~1000V |
Accuracy | 0.5 grade | |
Current monitoring | Current monitoring | Connect with current shunt base on rated current; CAI models only |
Accuracy | 5% | |
Insulation monitoring | Insulation resistance range | 1kΩ~10MΩ |
Warning and alarm range | 10kΩ~10MΩ | |
Accuracy | 1~10kΩ: ±1k; 10k~500k: ≤3% | |
System leakage capacitance | ≤5μF | |
Insulation monitoring speed | 500ms/cycle; 1000ms/cycle | |
Alarm method | LED indicator | |
Communication | RS485 interface, Modbus-RTU protocol | |
Installation | Wall-mounted installation or
DIN-rail installation (plastic stent included) |
|
Protection level | IP30 | |
Environment | Operating temperature | -40~+75℃ |
Storage temperature | -40~+125℃ | |
Relative humidity | <95%, without condensation | |
Altitude | <2000m |