Features
- A rugged, compact insulation resistance tester for residential and commercial electricians
- Performs insulation tests from 0.01 to 2000 MΩ
- Offers two insulation test voltages: 500 and 1000 V
- Includes live circuit detection to prevent insulation test if voltage >30 V is detected
- Measures resistance from 0.01 to 20.00 kΩ
- Measures AC/DC voltage from 0.1 to 600 V
- Includes auto-discharge of capacitive voltage for added user protection
- Provides lo-ohms earth-bond continuity (200 mA)
- Simplifies repetitive or hard-to-reach testing with the remote test probe
- Saves battery power with auto power off
- Presents results on a large, backlit display
- Features CAT IV 600 V overvoltage category rating
- Runs on 4 x AA alkaline batteries (NEDA 15 A or IEC LR6) for at least 1000 insulation tests
- Save battery power with auto power off
Applications
- Troubleshooting
- Commissioning
- Preventative maintenance
Specification
AC/DC Voltage Measurement | |
Accuracy | Range: 600 V Resolution: 0.1 V 50 to 400 Hz ± (%of Rdg + Digits): ±(2% + 3) |
Input Impedance | 3 MΩ (nominal), <100 pF |
Common Mode Rejection Ratio (1 kΩ unbalanced) | >60 dB at DC, 50 or 60 Hz |
Overload Protection | 600 V RMS or DC |
Earth Bond Resistance Measurement | |
Range/Resolution | 20 Ω:0.01 Ω 200 Ω:0.1 Ω 2000 Ω:1 Ω 20k Ω:0.01 kΩ |
Accuracy | ±(1.5% + 3) |
Overload Protection | 2 V rms or DC |
Open Circuit Test Voltage | >4 V, <8 V |
Short Circuit Current | >200 mA |
Insulation Specifications | |
Measurement Range | 0.01 to 2000 MΩ |
Test Voltage | 500 V, 1000 V |
Test Voltage Accuracy | +20%, -0% |
Short Circuit Current | 1 mA nominal |
Auto Discharge | Discharge time <0.5 second for C = 1 µF or less |
Live Circuit Indicator | Inhibit test if terminal voltage >30 V prior to initialization of test |
Maximum Capacitive Load | Operable with up to 1 µF load |
Measure Accuracy | 500 V: ±(1.5% + 5) 1000 V: ±(1.5% + 5) to 2000 MΩ, ±(10% + 3) above 2000 MΩ |