Fluke 1736 Power Quality Analyzer

The Fluke 1736 Power Quality Analyzer is a three-phase, multi-function, intelligent, and simple comprehensive test instrument specially developed for on-site testing. It is easy to use, large LCD color screen display, high resolution, bilingual operation interface in Chinese and English, and a vibration-proof structure shell.

It can measure 4 currents (ABC three-phase and neutral wire current),4 voltages (ABC three-phase voltage and neutral wire-to-ground voltage), the peak value of current and voltage, the maximum and minimum values within a period of time, three-phase current Balance, short-term voltage flicker, transformer K factor, active power, reactive power, apparent power, power factor, displacement power factor, active energy, reactive energy, apparent energy, harmonic ratio, total harmonic distortion, display current and voltage real-time waveforms, phasor diagrams, and harmonic ratio bar graphs; dynamically capture instantaneous changes in voltage and current, monitor starting current, monitor various power parameters and generate alarm events list, record test data for a long time and generate trend curves Picture and other various functions.

Contact us

Features

  • Real-time monitoring of power quality parameters
  • Reports and charts can be provided
  • Improve the reliability and stability of the power grid
  • Power quality analysis, diagnosis of grid quality
  • Remote monitoring, real time monitor power quality
  • Failure early warning, detection of potential equipment failures
  • Can record historical data to facilitate analysis and prediction of power quality change trends
  • Automatic alarm, automatically send an alarm signal when the power quality is abnormal
  • Optimize grid operation, reduce energy consumption, and improve grid efficiency

 

Application

  • Energy Metering and Billing
  • Smart grid construction and operation
  • Power system operation monitoring and analysis
  • Industrial production equipment power quality monitoring and analysis
  • Power quality improvement program design and implementation
  • Power system installation and operation inspection
  • Construction and operation monitoring of renewable energy power stations
  • power quality monitoring and management

Specification

Parameter Value
Frequency 40-70Hz / 0.01Hz / ±0.03Hz
True RMS Voltage 1.0-1000V / 0.1 / ±(0.5%+5dgt)
True RMS Line Voltage 1.0-2000V / 0.1 / ±(0.5%+5dgt)
DC Voltage 1.0-1000V / 0.1 / ±(1.0%+5dgt)
True RMS Current 10mA-6000A / 1mA / ±(0.5%+5dgt)
Phase Voltage Peak 1.0-1414V / 0.1 / ±(1.0%+5dgt)
Neutral Line voltage Peak 1.0-2828V / 0.1 / ±(1.0%+5dgt)
Current Peak 10mA-6000A / 1mA / ±(1.0%+5dgt)
CF 1.0~3.99 / 0.01 / ±(1%+2dgt)
4~9.99 / 0.01 / ±(5%+2dgt)
Active Power 0.000W-9999.9kW / 0.001W / ±(1%+3dgt)@PF>0.8
0.000W-9999.9kW / 0.001W / ±(1.5%+10dgt)@0.2<PF<0.8
Reactive Power, inductive or
capacitive
0.000Var-9999.9kVar / 0.001Var / ±(1%+3dgt)@PF<-0.5
0.000Var-9999.9kVar / 0.001Var / ±(1.5%+10dgt)@-0.5<PF<-0.2
Apparent Power 0.000VA-9999.9kVA / 0.001VA / ±(1%+3dgt)
Power Factor -1.000~1.000 / 0.001 / ±(1.5%+3dgt)@PF>0.5
-1.000~1.000 / 0.001 / ±(1.5%+10dgt)@0.2<PF<0.5
Active Electrical Energy 0.000Wh-9999.9MWh / 0.001Wh / ±(1%+3dgt)@PF>0.8
0.000Wh-9999.9MWh / 0.001Wh / ±(1.5%+10dgt)@0.2<PF<0.8
Reactive Electrical Energy, Inductive or Capacitive 0.000Varh-9999.9MVarh / 0.001Varh / ±(1%+3dgt)@PF<-0.5
0.000Varh-9999.9MVarh / 0.001Varh / ±(1.5%+10dgt)@-0.5<PF<-0.2
Apparent Electrical Energy 0.000VAh-9999.9MVAh / 0.001VAh / ±(1%+3dgt)
Phase Angle -179°~180° / 1° / ±2°
Tanφ (VA≥50VA) -32.76~32.76 / 0.001 / φ:±1°
DPF -1.000~1.000 / 0.001 / φ:±1°
Harmonic Ratio 1~50
(Vrms>50V)
0.0%~99.9% / 0.1% / ±(1%+5dgt)@1-20th
0.0%~99.9% / 0.1% / ±(1%+10dgt)@1-20th
0.0%~99.9% / 0.1% / ±(1%+15dgt)@1-20th
Harmonic Angle
(Vrms>50V)
-179°~180° / 1° / ±3°@1-25th
-179°~180° / 1° / ±10°@26-50th
Total Harmonic
Ratio (THD or THDF)≤50
0.0%~99.9% / 0.1% / ±(1%+5dgt)@1-20th
0.0%~99.9% / 0.1% / ±(1%+10dgt)@1-20th
0.0%~99.9% / 0.1% / ±(1%+15dgt)@1-20th
Distortion Factor
(DF or THD-R)≤50
-179°~180° / 1° / ±3°@1-25th
-179°~180° / 1° / ±10°@26-50th
Transformer K Factor 0.0%~99.9% / 0.1% / ±(1%+10dgt)
3 Phase Unbalance 0.0%~99.9% / 0.1% / ±(1%+10dgt)
Expert mode
Harmonic 0-50th
Total Harmonic distortion √ Per phase
Number of Transient Record
Voltage Flicker
Inrush current
Motor Starting Current detect 100s
Record 300 days @1 minute interval, 20 parameters each time
Alarm 12800 groups of alarm records, 40 kinds of parameters are optional
Peak Value
Screenshot Capacity 60
Comm port USB
Withstand Voltage 1min @ 3700Vac/50Hz,Case to line
Insulation 10MΩ
Safety Regulation IEC-61010,CATIII 1000V/IEC61010-31/IEC61326
Display Mode 640*480, 5.6inch, 116x88mm
Display Mode 240x170x68mm
Instrument Weight 1.6kgs(with battery),
power adapter0.9kgs,Packing size with protective box and transformer, <15KGS
Power 11.1V 7800mAhRechargeable lithium ion battery
Power Consumption 410mA, fully charged for 15 hours
Memory X (factory standard 32G memory card, can be replaced)
Waveform real-time display 4 voltages/4 currents