Feature
– Two delay modes can be set.
– Supports AC230V, AC/DC24V two kinds of working voltage.
– Ultra-wide delay range, 0.1 seconds – 10 days can be set.
– The working state of the relay is indicated by the LED indicator.
– Ultra-small size, only 18mm width, 35mm rail installation.
Specifications
GRT8-EC |
Function |
ON delay, Delay-off |
Supply terminals |
A1-A2(AC230V,AC380V),A1-A3(AC/DC24V) |
Voltage range |
AC230V(50-60Hz)orAC/DC24V,AC380V(50-60Hz) |
Power input |
AC max.6VA/1.3W |
Supply voltage tolerance |
-15%;+10% |
Supply indication |
green LED |
Time ranges |
0.1s-10day |
Time setting |
potentiometer |
Time deviation |
≤10% |
Repeat accuracy |
0.2%-set value stability |
Temperature coefficient |
0.05%/℃,at=20℃(0.05%°F, at=68°F) |
output |
1×SPDT |
Current rating |
1×10A(AC1) |
Switching voltage |
250VAC/24VDC |
Min. breaking capacity DC |
500mw |
Output indication |
red LED |
Mechanical life |
1×10^7 |
Electrical life(AC1) |
1×10^5 |
Reset time |
max.200ms |
operating temperature |
-20℃ to+55℃(-4°F to 131°F) |
Storage temperature |
-35℃to+75℃ (-22°F to 158°F) |
Mounting/DIN rail |
Din rail EN/IEC 60715 |
Protection degree |
IP40 for front panel/IP20 terminals |
Operating position |
any |
overvoltage cathegory |
Ⅲ. |
Pollution degree |
2 |
Max.cable size(mm²) |
solid wire max.1×2.5or 2×1.5/with sleeve max.1×2.5(AWG12) |
Dimensions |
90×18×64mm |
Weight |
52g |
Standards |
EN61812-1,IEC60947-5-1 |