Advantages
- High measurement resolution
- Low measurement uncertainty
- Wide measurement range
Applications Areas
It is used in Isolated Power Panels used in the electrical supply of Group 2 rooms in Medical Facilities (Hospitals, Health Centers, Dental Clinics, Aesthetic Centers, Animal Hospitals):
Group 2 rooms:
- Anesthetic rooms
- Operating rooms
- Operation preparation rooms
- Recovery room
- Cardiac catheterization rooms
- Intensive care units
- Angiographic examination rooms
Standards
- IEC 61557-8
- IEC 60364-7-710
Specification
Technical Specification | |
Rated Voltage | 230 Vac |
Supply Voltage | 24 Vac/dc |
Power Consuption | 8 W |
Frequency | 50/60 Hz |
Internal Resistance | ≥ 240 kΩ |
Insulation Measurement Range | 50 kΩ … 750 kΩ |
Insulation Measurement Resolution | ≤ 1 kΩ |
Insulation Measurement Uncertainty | < 0,5 mA |
Response Time | ≤ 2 s |
Current Measurement Range |
0 – 50 A |
Fault Relay Types | 1 x NO,NC |