Advantages:
- Suitable for DC charging stations for electric vehicles acc. to IEC/EN 61851-23:2014/AC:2016-06
- Insulation monitoring according to IEC/EN 61557-8
- Universal application in non-earthed AC-, DC-, AC/DC networks up to AC max. 250 V resp. DC max. 300 V
- Connection of an external coupling device RL 5898 for voltages up to AC 400 V / DC 500 V or RP 5898 for voltages up to AC 690 V / DC 1000 V possible
- Extended operating temperature range of – 40 … + 70 °C
- Very fast reaction time ≤ 1 s
- Optimised insulation resistance monitoring also during mains voltage variation
- Self-test every full operating hours
- Preventive fire and system protection
- Detection of symmetric and asymmetric insulation faults
- Easy adjustment of response values and setting parameter via Modbus
- Suitable for large leakage capacitances up to 5 μF
- Monitoring also with voltage-free mains
- Measuring circuit L(+)/L(-) with broken wire detection (can be switched off)
- Protective conductor PE1/PE2 with broken wire detection (can’t be switched off)
- With galvanic separated Modbus RTU interface
Features
- 2 separate adjustable response thresholds (using e.g. for pre-alarm and Alarm)
- Setting range of 1st response value (Pre-alarm): 20 kΩ … 500 kΩ
- Setting range of 2nd response value (alarm): 1 kΩ … 100 kΩ
- 1 changeover contacts each for insulation failures-Pre-alarm and -alarm
- Energized or de-energized on a trip can be selected for indicator relay
- With multicolor status LED to indicate the state of operation.
- Automatic and manual device self-test
- Alarm storage selectable
- Protection against manipulation by a sealable transparent cover
- External control input for combined test- / reset button with additional Stop of the measuring function
- 2 wide voltage input for auxiliary voltage
- Width 52.5 mm
Specification
Width: | 52,5 mm |
Classification: | For DC charging stations |
Response value: | 1 – 500 kΩ |
IMD type: | AC, DC, AC/DC |
Nominal voltage IT system: | AC 0 – 230, AC 0 – 690 (Coupling device), DC 0 – 230, DC 0 – 1000 (Coupling device) V |
Auxiliary voltage: | AC/DC |
Earth fault indicator: | Yes |
Approvals: | UL |
Response value type: | Adjustable |
Bus interface: | Modbus RTU |
Enclosure design: | Distribution board |
Type: | RN 5897/321 |