FEATURES
- Monitor the insulation resistance value:100~1000VDC;
- Insulation resistance measurement range 0KΩ~10MΩ;
- Detect DC voltage value, range 100 ~ 1000 VDC;
- RS485 communication, MODBUS RTU communication;
- DC voltage reverse connection alarm function;
- External self-test of insulation monitoring module;
- Ground line disconnection detection;
- Two types of work models available: Automatically switching battery model (Non-equilibrium battery method, using the local power supply system); Fixed power network model (balanced battery method, using the local power supply system).
APPLICATIONS
- Photovoltaic system;
- DC systems such as DC grids;
- Electric vehicle DC charging system;
- Energy storage system.
Specification
Parameter | Value | ||
Power supply | 10-30VDC, Power 3w | ||
DC voltage range | 100V~1000V | ||
DC voltage
measurement accuracy |
≤2V+0.5% | ||
Insulation resistance
measurement range |
1KΩ~10MΩ
(DC System voltage:100V~1000V) |
||
Insulation monitoring accuracy
((When :DC voltage:100V-1000V) |
CY range | Resistance range | Accuracy |
0~0.8μF | ≤60kΩ | ≤3kΩ | |
60kΩ<R≤1MΩ | ≤5% | ||
0.8μF ~3μF | ≤60kΩ | ≤6kΩ | |
60kΩ<R≤1MΩ | ≤20% | ||
Insulation monitoring function switching times | 50*105 times | ||
Self-test circuit switch frequency | ≤1×105 | ||
Insulation resistance value
update time after turning on |
After insulation monitoring is turned on, the time until the effective resistance value can be read for the first time | 0.7s~2s | |
Insulation resistance value
update time |
Switch the insulation resistance until the module can read the switched insulation resistance value. | 0.5s~3s | |
Off-line pressure test | <2mA | ||
Standard | IEC 61851-23 (2014-03):2014-11 | ||
Humidity | 85% | ||
Storage temperature | – 55°C ~90°C | ||
Operating temperature | – 40°C ~75°C |