Schneider LC1D09P7 IEC AC contactor

Schneider LC1D09P7 TeSys D AC contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps.

This 9A inductive 3-pole IEC contactor can be mounted on a DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor ratings for international acceptance. A contactor is rated for 20HP at 200-208VAC, 25HP at 240VAC, 60HP at 480VAC, and 60HP at 600VAC three phase.

Contact us
Category:

Features

  • Withstand high voltage and high current load, long service life.
  • High sensitivity and fast response speed can ensure the accuracy of circuit operation.
  • The operation is simple, the installation is convenient, and it can adapt to various circuit requirements.
  • Small in size, lightweight and takes up little space.
  • It can withstand high temperature, low temperature and humid environment, and can improve the stability of the circuit.
  • Good sealing performance, can prevent foreign matter from entering the
  • High power, suitable for the control of high power circuits.
  • Small noise, small vibration, stable use.
  • Has good strength and durability

Applications

  • Commonly used in the control of large air conditioning systems.
  • Lighting system to control the switch of lights.
  • Used for compressor control in refrigeration systems.
  • In motor control, the motor can realize normal start-stop and reverse operation.
  • Used in power capacitor banks to control the connection and disconnection of capacitors
  • Used in the automation control of industrial production lines

 

Specification

 
Motor power kW 2.2 kW 220…230 V AC 50/60 Hz AC-3)
4 kW 380…400 V AC 50/60 Hz AC-3)
4 kW 415…440 V AC 50/60 Hz AC-3)
5.5 kW 500 V AC 50/60 Hz AC-3)
5.5 kW 660…690 V AC 50/60 Hz AC-3)
2.2 kW 400 V AC 50/60 Hz AC-4)
2.2 kW 220…230 V AC 50/60 Hz AC-3e)
4 kW 380…400 V AC 50/60 Hz AC-3e)
4 kW 415…440 V AC 50/60 Hz AC-3e)
5.5 kW 500 V AC 50/60 Hz AC-3e)
5.5 kW 660…690 V AC 50/60 Hz AC-3e)
Maximum Horse Power Rating 1 hp 230/240 V at AC 50/60 Hz for 1 phase
2 hp 200/208 V at AC 50/60 Hz for 3 phase
2 hp 230/240 V at AC 50/60 Hz for 3 phase
5 hp 460/480 V at AC 50/60 Hz for 3 phase
7.5 hp 575/600 V at AC 50/60 Hz for 3 phase
0.33 hp 115 V at AC 50/60 Hz for 1 phase
Compatibility code LC1D
Pole contact composition 3 NO
Contact compatibility M2
Protective cover With
[Ith] conventional free air thermal current 25 A 140 °F (60 °C) power circuit
10 A 140 °F (60 °C) signalling circuit
Irms rated making capacity 250 A 440 V power circuit IEC 60947
140 A AC signalling circuit IEC 60947-5-1
250 A DC signalling circuit IEC 60947-5-1
Rated breaking capacity 250 A 440 V power circuit IEC 60947
[Icw] rated short-time withstand current 105 A 104 °F (40 °C) – 10 s power circuit
210 A 104 °F (40 °C) – 1 s power circuit
30 A 104 °F (40 °C) – 10 min power circuit
61 A 104 °F (40 °C) – 1 min power circuit
100 A – 1 s signalling circuit
120 A – 500 ms signalling circuit
140 A – 100 ms signalling circuit
Associated fuse rating 10 A gG signalling circuit IEC 60947-5-1
25 A gG <= 690 V type 1 power circuit
20 A gG <= 690 V type 2 power circuit
Average impedance 2.5 mOhm – Ith 25 A 50 Hz power circuit
Power dissipation per pole 1.56 W AC-1
0.2 W AC-3
0.2 W AC-3e
[Ui] rated insulation voltage Power circuit 690 V IEC 60947-4-1
Power circuit 600 V CSA
Power circuit 600 V UL
Signalling circuit 690 V IEC 60947-1
Signalling circuit 600 V CSA
Signalling circuit 600 V UL
Overvoltage category III
Pollution degree 3
[Uimp] rated impulse withstand voltage 6 kV IEC 60947
Safety reliability level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability 15 Mcycles
Electrical durability 0.6 Mcycles 25 A AC-1 <= 440 V
2 Mcycles 9 A AC-3 <= 440 V
2 Mcycles 9 A AC-3e <= 440 V
Control circuit type AC 50/60 Hz standard
Coil technology Without built-in suppressor module
Control circuit voltage limits 0.3…0.6 Uc -40…158 °F (-40…70 °C) drop-out AC 50/60 Hz
0.8…1.1 Uc -40…140 °F (-40…60 °C) operational AC 50 Hz
0.85…1.1 Uc -40…140 °F (-40…60 °C) operational AC 60 Hz
1…1.1 Uc 140…158 °F (60…70 °C) operational AC 50/60 Hz
Inrush power in VA 70 VA 60 Hz 0.75 68 °F (20 °C))
70 VA 50 Hz 0.75 68 °F (20 °C))
Hold-in power consumption in VA 7.5 VA 60 Hz 0.3 68 °F (20 °C))
7 VA 50 Hz 0.3 68 °F (20 °C))
Heat dissipation 2…3 W 50/60 Hz
Operating time 12…22 ms closing
4…19 ms opening
Maximum operating rate 3600 cyc/h 140 °F (60 °C)
Connections – terminals Power circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²) flexible without cable end
Power circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²) flexible without cable end
Power circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²) flexible with cable end
Power circuit screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²) flexible with cable end
Power circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²) solid without cable end
Power circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²) solid without cable end
Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²) flexible without cable end
Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²) flexible without cable end
Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²) flexible with cable end
Control circuit screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²) flexible with cable end
Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²) solid without cable end
Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²) solid without cable end
Tightening torque Power circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm
Power circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals pozidriv No 2
Power circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals pozidriv No 2
auxiliary contact composition 1 NO + 1 NC
Auxiliary contacts type Mechanically linked 1 NO + 1 NC IEC 60947-5-1
Mirror contact 1 NC IEC 60947-4-1
Signalling circuit frequency 25…400 Hz
Minimum switching voltage 17 V signalling circuit
Minimum switching current 5 mA signalling circuit
Insulation resistance > 10 MOhm signalling circuit
Non-overlap time 1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
Mounting Support Rail
Plate