Applications of MCR-S-1-5-UI Current Measuring Transducer
- Power generation and transmission distribution stations
- Building management
- Load dispatch centers
- Original Equipment Manufacturers (OEMs) for power equipment
- High-Tension (HT) and Low-Tension (LT) panels
- Substation automation
- Supervisory Control and Data Acquisition (SCADA)
- Local and central monitoring systems
Specification of MCR-S-1-5-UI Current Measuring Transducer
Total error | ≤ 1.5 % (Temperature range) |
Maximum power dissipation for nominal condition | 2.2 W |
Measuring category | III |
Test voltage output/power supply | 500 V AC (50 Hz, 60 s) |
Test voltage input/output | 4 kV AC (50 Hz, 60 s) |
Test voltage input/power supply | 4 kV AC (50 Hz, 60 s) |
Protective circuit | Surge protection; 33 V suppressor diode |
Step response (10-90%) | 330 ms (AC) |
40 ms (DC) | |
Temperature coefficient, typical | < 0.025 %/K |
Maximum transmission error | < 0.5 % (of nominal range value under nominal conditions) |
Rated insulation voltage | 300 V AC (to earth) |
Supply | |
Supply voltage range | 20 V DC … 30 V DC |
Max. current consumption | < 50 mA (without load) |