Feature
- Universal AC input/Full range
- Protections: Short circuit / Overload / Over voltage
- Cooling by free air convection
- Can be installed on DIN rail TS-35/7.5 or 15
- Class I, Div 2 Hazardous Locations T4
- LED indicator for power on
- DC OK relay contact
- No load power consumption<0.75W
- 100% full load burn-in test
- 3 years warranty
Application
- Industrial control system
- Mechanical and electrical equipment
- Electronic instruments
- Test and measurement instrument
- Laser related machine
- Charging related equipment
- Household appliances
- Power Sourcing Equipment of PoE
Specification
MODEL | MDR-60-5 | MDR-60-12 | MDR-60-24 | MDR-60-48 | |
OUTPUT |
DC VOLTAGE | 5V | 12V | 24V | 48V |
RATED CURRENT | 10A | 5A | 2.5A | 1.25A | |
CURRENT RANGE | 0 ~ 10A | 0 ~ 5A | 0 ~ 2.5A | 0 ~ 1.25A | |
RATED POWER | 50W | 60W | 60W | 60W | |
RIPPLE & NOISE (max.) Note.2 | 80mVp-p | 120mVp-p | 150mVp-p | 200mVp-p | |
VOLTAGE ADJ. RANGE | 5 ~ 6V | 12 ~ 15V | 24 ~ 30V | 48 ~ 56V | |
VOLTAGE TOLERANCE Note.3 | ±2.0% | ±1.0% | ±1.0% | ±1.0% | |
LINE REGULATION | ±1.0% | ±1.0% | ±1.0% | ±1.0% | |
LOAD REGULATION | ±1.5% | ±1.0% | ±1.0% | ±1.0% | |
SETUP, RISE TIME Note.5 | 500ms, 30ms/230VAC 500ms, 30ms/115VAC at full load | ||||
HOLD UP TIME (Typ.) | 50ms/230VAC 20ms/115VAC at full load | ||||
INPUT |
VOLTAGE RANGE | 85 ~ 264VAC 120 ~ 370VDC | |||
FREQUENCY RANGE | 47 ~ 63Hz | ||||
EFFICIENCY (Typ.) | 78% | 86% | 88% | 87% | |
AC CURRENT (Typ.) | 1.8A/115VAC 1A/230VAC | ||||
INRUSH CURRENT (Typ.) | COLD START 30A/115VAC 60A/230VAC | ||||
LEAKAGE CURRENT | <1mA / 240VAC | ||||
PROTECTION |
OVERLOAD |
105 ~ 150% rated output power | |||
Protection type : Constant current limiting, recovers automatically after fault condition is removed | |||||
OVER VOLTAGE |
6.25 ~ 7.25V | 15.6 ~ 18V | 31.2 ~ 36V | 57.6 ~ 64.8V | |
Protection type : Shut down o/p voltage, re-power on to recover | |||||
FUNCTION | DC OK SIGNAL | Relay contact rating(max.): 30V/1A resistive | |||
ENVIRONMENT |
WORKING TEMP. | -20 ~ +70℃ (Refer to “Derating Curve”) | |||
WORKING HUMIDITY | 20 ~ 90% RH non-condensing | ||||
STORAGE TEMP., HUMIDITY | -40 ~ +85℃, 10 ~ 95% RH | ||||
TEMP. COEFFICIENT | ±0.03%/℃ (0 ~ 50℃) | ||||
VIBRATION | Component : 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes ; Mounting : Compliance to IEC60068-2-6 | ||||
SAFETY & EMC (Note 4) |
SAFETY STANDARDS | Ul508, UL62368-1, TUV BS EN/EN62368-1,Class I, Div. 2 Group A, B, C, D Hazardous Locations T4, EAC TP TC 004, BSMI CNS14336-1, AS/NZS 60950.1 , IS13252(Part1)/IEC60950-1(except 48V) approved | |||
WITHSTAND VOLTAGE | I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC | ||||
ISOLATION RESISTANCE | I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25℃/ 70% RH | ||||
EMC EMISSION | Compliance to BS EN/EN55032 (CISPR32), BS EN/EN61204-3 Class B, BS EN/EN61000-3-2,-3, EAC TP TC 020, CNS13438 Class B | ||||
EMC IMMUNITY |
Compliance to BS EN/EN61000-4-2, 3, 4, 5, 6, 8, 11, BS EN/EN55035, BS EN/EN61000-6-2, BS EN/EN61204-3, heavy industry level, EAC TP TC 020 | ||||
OTHERS |
MTBF | 2355.2K hrs min. Telcordia SR-332 (Bellcore) ; 489.9K hrs min. MIL-HDBK-217F (25℃) | |||
DIMENSION | 40*90*100mm (W*H*D) | ||||
PACKING | 0.33Kg; 42pcs/14.8Kg/0.82CUFT | ||||
NOTE | 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.” (as available on http://www.meanwell.com) 5. Length of set up time is measured at first cold start. Turning ON/OFF the power supply may lead to increase of the set up time. 6. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft}. |